WIDP-WGI Wireless Gateway
Fike and SWIFT SLC Device Installation
FCP-300/FCP-300ECS Manual —
P/N LS10145-002FK-E:A 3/12/2021
73
7.6.1 SLC Devices with DIP Switches
Input and relay module addresses are set using the DIP switches on the module board. The chart below shows the available
addresses. For example, to select address 3, place DIP switches 1 and 2 in the up position. The range of valid addresses is 1-
127. 0 is an invalid address.
Figure 7.6 SD SLC Device Addressing Using DIP Switches
7.7 WIDP-WGI Wireless Gateway
For more information regarding Gateway wiring instructions, see SWIFT manual LS10036-000FH-E or LS10036-000SK-E.
7.7.1 Power Connections for the Gateway
The FIK-W-WGI Wireless Gateway acts as a bridge between a group of wireless fire devices and a SLC loop on the FIK-
300/ECS. It is powered by the SLC loops or by a regulated, external 24 VDC UL listed power supply. For updated details
about wireless devices, system setup, and operation, see the
SWIFT
Smart Wireless Integrated Fire Technology Instruction
Manual P/N LS10036-001FK-E
.
NOTE:
The WIDP-WGI or SK-WGI, as part of the wireless network, has been tested for compliance with the Federal Communications
Commission (FCC) requirements of the United States Government. It has not been evaluated for use outside the USA. Use of this system
outside the USA is subject to local laws and rules to which this product may not conform. It is the sole responsibility of the user to determine
if this product may be legally used outside the USA.
NOTE:
It is recommended to use the same wire gauge if there are multiple connections to the same terminal.
Summary of Contents for FCP-300
Page 169: ...Cut Along the Dotted Line ...
Page 171: ...Cut Along the Dotted Line ...
Page 173: ...Cut Along the Dotted Line ...
Page 175: ...Cut Along the Dotted Line ...