INSTALLATION AND MAINTENANCE INSTRUCTIONS

BEFORE INSTALLING

If the modules will be installed in an existing operational system, inform the 
operator and local authority that the system will be temporarily out of service. 
Disconnect the power to the control panel before installing the modules. This 
system contains static sensitive components. Always ground yourself with a 
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The module housing should also be grounded.

NOTICE: This manual should be left with the owner/user of this equipment.

GENERAL DESCRIPTION

The FIK-CZ-6 Six Zone Interface Module is intended for use in an intelligent 
alarm system. Each module provides an interface between the intelligent 
alarm system and a conventional alarm system loop. A common SLC input is 
used for all modules, and the initiating device loops share a common super-
visory supply and ground. Otherwise, each monitor operates independently 
from the others. Each module has its own unique address.

A pair of rotary code switches is used to set the address of the first module 
from 01 to 94 (or 01 to 154 for panels that support 159 addresses). The re-
maining modules are automatically assigned to the next five higher addresses. 
Provisions are included for disabling a maximum of two unused modules to 
release the addresses to be used elsewhere. Each module also has panel con-
trolled bicolor LED indicators. The panel can cause the LEDs to blink, latch 
on, or latch off.

Included: 

(5) 1 x 4 Terminal Blocks            (2) 1¼” Stand offs           (3) Shunts

               

                        

                    

(4) Machine Screws   (2) Nuts             (1) Long Power Supply Jumper

   

           

                  

(6) 3.9k Ohm End of Line Resistors

         

 C0202-00

Shipped on Board:

 

(2)  Shunts in Class A/B position 

 

(Shipped in Class B position, remove shunts for Class A)

COMPATIBILITY REQUIREMENTS

To ensure proper operation, this module shall be connected to a compatible 
Fike system control panel (list available from Fike). A list of compatible two-
wire System Sensor® Smoke detectors for use with the FIK-CZ-6 is available 
on the Fike website.

COMPONENTS

The following is a description of the FIK-CZ-6 mounting framework:

•  One or two FIK-CZ-6 modules can be installed in a FIK-BB-2 cabinet

FIGURE 1. FIK-BB-2 CABINET

 

0

1

2 3 4 5 6

7

8

9

0

7

8

6

5

4

3

2

1

9

10

11

12

13

14

15

BASE 

ADDRESS

ADDRESS

DISABLE

NONE

ONE

TWO

THREE

0

1

2 3 4 5 6

7

8

9

0

7

8

6

5

4

3

2

1

9

BASE 

ADDRESS

ADDRESS

DISABLE

NONE

ONE

TWO

THREE

10

11

12

13

14

15

 C0234-05

The FIK-BB-2 cabinet has a built-in chassis that will accommodate one or two 
FIK-CZ-6 modules. For cabinet dimensions refer to the FIK-BB-2 instruction 
manual.

The front FIK-CZ-6 module positions of each chassis are offset below the rear 
FIK-CZ-6 module positions so that all of the status indicators are visible.

INSTALLATION STEPS

1.  Cabinet Mounting 

In a clean, dry area, mount the backbox using the four holes provided in the 
back surface of the cabinet. (See Figure 2.)

I56-6896-000

 704 SW 10th Street

 Blue Springs, MO 64015

 Phone: 816.229.3405; Fax: 816.228.9277 

www.fike.com

FIK-CZ-6 

Six Zone Interface Module

SPECIFICATIONS

Normal Operating Voltage: 

15-32 VDC

Stand-By Current: 

2.3 mA @ 24V

Alarm Current: 

40 mA (assumes all six LEDs solid on) 

Temperature Range: 

32ºF to 120ºF ( 0ºC to 49ºC)

Humidity: 

10 to 93% Non-condensing

Dimensions: 

6.8" H x 5.8" W x 1.0" D

Accessories: 

FIK-BB-2 Cabinet and chassis

Wire Gauge: 

12-18 AWG 

Max. IDC Wiring Resistance: 

25 ohms

External Power Supply Voltage: 

Regulated 24VDC

Ripple Voltage: 

0.1 volts RMS maximum

IDC: 

(Supervised and power limited)

 

DC Voltage: 

18-28 volts power limited

 Frequency: 

DC

 

Alarm Current: 

90mA per circuit

 

Standby Current 6 circuits:  

42mA Maximum @18VDC

 

 

56mA Maximum @24VDC

 

 

66mA Maximum @28VDC

R

  

I56-6896-000 

 

 1/15/2021

http://www.fike.com/06-912

For system/product documentation including 

installation, operation, and maintenance, 

scan QR code or enter URL provided. 

Summary of Contents for FIK-CZ-6

Page 1: ...this module shall be connected to a compatible Fike system control panel list available from Fike A list of compatible two wire System Sensor Smoke detectors for use with the FIK CZ 6 is available on the Fike website COMPONENTS The following is a description of the FIK CZ 6 mounting framework One or two FIK CZ 6 modules can be installed in a FIK BB 2 cabinet FIGURE 1 FIK BB 2 CABINET 0 1 2 3 4 5 6...

Page 2: ...ass B operation if the shunt for Address Dis able is placed on two and the base switch is set to 28 the modules will be assigned to 28 29 30 and 31 while disabling the highest two positions NOTE Place unused shunts on single pin to store on board for future use WIRING NOTES Power limited circuits must employ type FPL FPLR or FPLP cable as required by Article 760 of the NEC All wiring must be in ac...

Page 3: ... DEVICE CONNECT MODULES TO LISTED COMPATIBLE HONEYWELL FARENHYT SERIES CONTROL PANELS ONLY SIGNAL LINE CIRCUIT SLC 32 VDC MAX SEE PANEL INSTRUCTION MANUAL FOR WIRE REQUIREMENTS CLASS A IDC TYPICAL A B SELECT A B SELECT DISABLE 1 DISABLE 2 IDC 2 IDC 3 POWER TO THE NEXT INTERFACE MODULE MUST BE EXTERNALLY SWITCHED TO RESET THE DETECTORS AN FRM 1 RELAY CONTROL MODULE CAN BE USED TO SWITCH POWER FROM ...

Page 4: ...st harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or te...

Reviews: