INSTALLATION AND MAINTENANCE INSTRUCTIONS
BEFORE INSTALLING
If the modules will be installed in an existing operational system, inform the
operator and local authority that the system will be temporarily out of service.
Disconnect the power to the control panel before installing the modules. This
system contains static sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The module housing should also be grounded.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The FIK-CZ-6 Six Zone Interface Module is intended for use in an intelligent
alarm system. Each module provides an interface between the intelligent
alarm system and a conventional alarm system loop. A common SLC input is
used for all modules, and the initiating device loops share a common super-
visory supply and ground. Otherwise, each monitor operates independently
from the others. Each module has its own unique address.
A pair of rotary code switches is used to set the address of the first module
from 01 to 94 (or 01 to 154 for panels that support 159 addresses). The re-
maining modules are automatically assigned to the next five higher addresses.
Provisions are included for disabling a maximum of two unused modules to
release the addresses to be used elsewhere. Each module also has panel con-
trolled bicolor LED indicators. The panel can cause the LEDs to blink, latch
on, or latch off.
Included:
(5) 1 x 4 Terminal Blocks (2) 1¼” Stand offs (3) Shunts
(4) Machine Screws (2) Nuts (1) Long Power Supply Jumper
(6) 3.9k Ohm End of Line Resistors
C0202-00
Shipped on Board:
(2) Shunts in Class A/B position
(Shipped in Class B position, remove shunts for Class A)
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Fike system control panel (list available from Fike). A list of compatible two-
wire System Sensor® Smoke detectors for use with the FIK-CZ-6 is available
on the Fike website.
COMPONENTS
The following is a description of the FIK-CZ-6 mounting framework:
• One or two FIK-CZ-6 modules can be installed in a FIK-BB-2 cabinet
FIGURE 1. FIK-BB-2 CABINET
0
1
2 3 4 5 6
7
8
9
0
7
8
6
5
4
3
2
1
9
10
11
12
13
14
15
BASE
ADDRESS
ADDRESS
DISABLE
NONE
ONE
TWO
THREE
0
1
2 3 4 5 6
7
8
9
0
7
8
6
5
4
3
2
1
9
BASE
ADDRESS
ADDRESS
DISABLE
NONE
ONE
TWO
THREE
10
11
12
13
14
15
C0234-05
The FIK-BB-2 cabinet has a built-in chassis that will accommodate one or two
FIK-CZ-6 modules. For cabinet dimensions refer to the FIK-BB-2 instruction
manual.
The front FIK-CZ-6 module positions of each chassis are offset below the rear
FIK-CZ-6 module positions so that all of the status indicators are visible.
INSTALLATION STEPS
1. Cabinet Mounting
In a clean, dry area, mount the backbox using the four holes provided in the
back surface of the cabinet. (See Figure 2.)
I56-6896-000
704 SW 10th Street
Blue Springs, MO 64015
Phone: 816.229.3405; Fax: 816.228.9277
www.fike.com
FIK-CZ-6
Six Zone Interface Module
SPECIFICATIONS
Normal Operating Voltage:
15-32 VDC
Stand-By Current:
2.3 mA @ 24V
Alarm Current:
40 mA (assumes all six LEDs solid on)
Temperature Range:
32ºF to 120ºF ( 0ºC to 49ºC)
Humidity:
10 to 93% Non-condensing
Dimensions:
6.8" H x 5.8" W x 1.0" D
Accessories:
FIK-BB-2 Cabinet and chassis
Wire Gauge:
12-18 AWG
Max. IDC Wiring Resistance:
25 ohms
External Power Supply Voltage:
Regulated 24VDC
Ripple Voltage:
0.1 volts RMS maximum
IDC:
(Supervised and power limited)
DC Voltage:
18-28 volts power limited
Frequency:
DC
Alarm Current:
90mA per circuit
Standby Current 6 circuits:
42mA Maximum @18VDC
56mA Maximum @24VDC
66mA Maximum @28VDC
R
1
I56-6896-000
1/15/2021
http://www.fike.com/06-912
For system/product documentation including
installation, operation, and maintenance,
scan QR code or enter URL provided.