background image

CAUTION

Do not detach the door of the pull station during installation. The door of 
the pull station cannot be reattached to the backplate after the backplate has 
already been installed onto an electrical box.

CAUTION

Install the FIK-PULL-SA addressable pull station in accordance with these in-
structions, applicable NFPA standards, national and local Fire and Electrical 
codes and the requirements of the AHJ (Authority Having Jurisdiction). Regu-
lar testing of the devices should be conducted in accordance with the appro-
priate NFPA standards. Failure to follow these directions may result in failure 
of the device to report an alarm condition. For specific information regarding 
sensor spacing, placement, and special applications, refer to NFPA 72 or the 
System Smoke Detector Application Guide, available from System Sensor.

Fike is not responsible for devices that have been improperly installed, tested 
or maintained.

ADA Compliance 

For ADA compliance, if the clear floor space only allows forward approach to 
an object, the maximum forward reach height allowed is 48 inches (121.92 
cm). If the clear floor space allows parallel approach by a person in a wheel-
chair, the maximum side reach allowed is 54 inches (137.16 cm).

OPERATION

To activate the single-action pull station:

Pull down on the handle. The word ‘ACTIVATED’ appears after the handle is 
pulled down. This will remain until the pull sta tion is reset. 
The pull station includes one Single Pole, Single Throw (SPST) Normally Open 
(N/O) switch which closes upon activation of the pull station.

To reset the pull station: 

1. Insert the key into the lock and rotate ¼ turn counterclockwise.
2. Open the door until the handle returns to normal.
3. Close and lock the door.
NOTE: Closing the door automatically resets the switch to the ‘Normal’ posi-
tion. Open ing the door will not activate or deactivate the alarm switch.

 
 

Note  –  Opening  the  pull 
station  door  will  not  activate 
or deactivate the alarm switch. 

NORMAL

ACTIV

ATED

4     3     2     1

0

0

10

11

12

13

14

15

1

1

2

2

3

3

4

4

TENS

ONES

6

6

7

7

8

8

9

9

5

5

 

LOOP

REFER    TO   DOCUMENT

M

ADDRESS

 

ADDRESS

LOOP

0

0

10

11

12

13

14

15

1

1

2

2

3

3

4

4

6

6

7

7

8

8

9

9

5

5

LED

ROTARY ADDRESS SWITCHES

LED OPERATION

Alarm: 

Steady RED

Normal: 

Flash GREEN

Note: LED is 
visible through 
translucent handle.

PRODUCT IDENTIFICATION LABEL

P0130-02

FIGURE 3. 

DEVICE AND SYSTEM SECURITY

Before installing this product ensure that the 
tamper seal on the packaging is present and 
unbroken and the product has not been tampered 
with since leaving the factory. Do not install this 
product if there are any indications of tampering. 
If there are any signs of tampering the product 
should be returned to the point of purchase.
It is the responsibility of the system owner to 
ensure that all system components, i.e. devices, 
panels, wiring etc., are adequately protected to 
avoid tampering of the system that could result 
in information disclosure, spoofing, and integrity 
violation.

  2 

I56-6959-001 

  

©2021. 10/5/2021

Fike

®

 is a registered trademark of Fike Corporation. System Sensor® is a registered trademark of Honeywell International, Inc. 

Reviews: