CAUTION
Do not detach the door of the pull station during installation. The door of
the pull station cannot be reattached to the backplate after the backplate has
already been installed onto an electrical box.
CAUTION
Install the FIK-PULL-SA addressable pull station in accordance with these in-
structions, applicable NFPA standards, national and local Fire and Electrical
codes and the requirements of the AHJ (Authority Having Jurisdiction). Regu-
lar testing of the devices should be conducted in accordance with the appro-
priate NFPA standards. Failure to follow these directions may result in failure
of the device to report an alarm condition. For specific information regarding
sensor spacing, placement, and special applications, refer to NFPA 72 or the
System Smoke Detector Application Guide, available from System Sensor.
Fike is not responsible for devices that have been improperly installed, tested
or maintained.
ADA Compliance
For ADA compliance, if the clear floor space only allows forward approach to
an object, the maximum forward reach height allowed is 48 inches (121.92
cm). If the clear floor space allows parallel approach by a person in a wheel-
chair, the maximum side reach allowed is 54 inches (137.16 cm).
OPERATION
To activate the single-action pull station:
Pull down on the handle. The word ‘ACTIVATED’ appears after the handle is
pulled down. This will remain until the pull sta tion is reset.
The pull station includes one Single Pole, Single Throw (SPST) Normally Open
(N/O) switch which closes upon activation of the pull station.
To reset the pull station:
1. Insert the key into the lock and rotate ¼ turn counterclockwise.
2. Open the door until the handle returns to normal.
3. Close and lock the door.
NOTE: Closing the door automatically resets the switch to the ‘Normal’ posi-
tion. Open ing the door will not activate or deactivate the alarm switch.
Note – Opening the pull
station door will not activate
or deactivate the alarm switch.
NORMAL
ACTIV
ATED
4 3 2 1
0
0
10
11
12
13
14
15
1
1
2
2
3
3
4
4
TENS
ONES
6
6
7
7
8
8
9
9
5
5
LOOP
REFER TO DOCUMENT
M
ADDRESS
ADDRESS
LOOP
0
0
10
11
12
13
14
15
1
1
2
2
3
3
4
4
6
6
7
7
8
8
9
9
5
5
LED
ROTARY ADDRESS SWITCHES
LED OPERATION
Alarm:
Steady RED
Normal:
Flash GREEN
Note: LED is
visible through
translucent handle.
PRODUCT IDENTIFICATION LABEL
P0130-02
FIGURE 3.
DEVICE AND SYSTEM SECURITY
Before installing this product ensure that the
tamper seal on the packaging is present and
unbroken and the product has not been tampered
with since leaving the factory. Do not install this
product if there are any indications of tampering.
If there are any signs of tampering the product
should be returned to the point of purchase.
It is the responsibility of the system owner to
ensure that all system components, i.e. devices,
panels, wiring etc., are adequately protected to
avoid tampering of the system that could result
in information disclosure, spoofing, and integrity
violation.