PREFACE
FIKE CORPORATION
Page 4 of 43
SHP Product Manual
UL S2203
Rev. No: 3, 04/02
Manual P/N: 06-130
FM 0Z8A0.AY
1.5
SYMBOLS USED IN THIS MANUAL
The following symbols are used throughout this manual.
NOTE:
Used to call your attention to an important procedure, function or operational
procedure.
CAUTION:
Used to identify functions or procedures of utmost importance.
WARNING:
Used to identify functions and/or procedures that could cause property damage
or personal injury if the procedures identified in this manual are not followed.
1.6
SAFETY NOTICES
Be certain to read all the following warnings and cautions before installing or using this device.
Accidental damage to the device could result if these warnings and cautions are not heeded!
CAUTION:
The SHP contains static sensitive components. Handle the electronics by
the edges only and avoid touching the integrated components. Keep the
electronics in the protective static bags it was shipped in until time for
installation. Always ground yourself with a proper wrist strap before handling
the module(s). If the installer is grounded at all times, damage due to static
discharge will not occur. If the module requires repair or return to Fike, it
must be shipped in an anti-static bag.
CAUTION:
To ensure proper system operation after installation of the SHP, this device
must be tested in accordance with NFPA 72 - 1999 edition. Re-acceptance
testing is required after any change, addition or deletion of system
components, or after any modification, repair or adjustment to system
hardware or wiring.
WARNING:
Failure to disconnect power to the releasing circuit(s) and disarm the
solenoid(s) or any other "critical operation" contacts prior to system testing
may cause accidental activation of the system.