OPERATIONS
FIKE CORPORATION
Page 32 of 43
SHP Product Manual
UL S2203
Rev. No: 3, 04/02
Manual P/N: 06-130
FM 0Z8A0.AY
5.11
ALARM OPERATION (IN SPRINKLER MODE)
Operation is same as in the Suppression mode, except:
Alarm audibles and pre-discharge audibles remain on during subsequent states.
Abort operation is not available.
Upon waterflow input activation, system enters release state. Typical response changes to:
Piezo:
Chirp (On & Off pattern) until silenced.
Release LED:
Flash. After silencing, illuminate steady.
Alarm, Waterflow Relays:
Activate.
Alarm, Pre-discharge, Waterflow Audibles:
Activate until silenced.
Solenoid Circuit:
Activate.
Waterflow outputs are latching as they remain on after deactivation of waterflow input.
Manual Release activation does not activate waterflow output.
Manual Release operation does activate both the alarm and pre-discharge audibles.
NOTE:
During activation of multiple events, piezo priority is alarm over supervisory over trouble.
5.12
SUPERVISORY OPERATION
Upon activation of a supervisory input, system enters supervisory state. Typical response includes:
Piezo:
Warble (On & Off pattern) until silenced.
Supervisory LED:
Flash. After silencing, illuminate steady.
Supervisory Relay:
Activate.
Supervisory Audibles:
Activate until silenced.
Upon deactivation of the supervisory input, typical system response includes:
Piezo:
Off
Supervisory LED:
Flash every 10 seconds until manual reset.
Supervisory Relay:
Off.
Supervisory Audibles:
Off.
Diagnostic LED:
Displays code corresponding to supervisory input.
5.13
TROUBLE OPERATION
Upon occurrence of a trouble condition, system enters trouble state. Typical response includes:
Piezo:
Steady on until silenced.
Trouble LED:
Flash. After silencing, illuminate steady.
Trouble Relay:
Activate.
Diagnostic LED:
Displays code or codes corresponding to trouble conditions.
Upon Trouble clear (except for latching troubles), system performs a trouble-clear-reset. Typical
response includes:
Piezo:
Off
Trouble LED:
Blink every 10 seconds until manual reset.
Trouble Relay:
Off.
Diagnostic LED:
Displays code or codes corresponding to trouble conditions.