MEGA SD - Cod.197DD8100
GB
START-Up AND OpERATION
Press the K4 key to return to the
OPErAT.
PArAMETErS
menu from submenus.
• rotation time
This is the time after which compressor start-up priorities are reassigned so that the work load is evenly distributed between the
machines available over a long period of time.
• reaction times
T ON
when the control system activates a compressor following a reduction in network pressure, timer T ON is started: at the
end of this count, the system checks network pressure to establish whether another compressor must be started.
T OFF
when the control system deactivates a compressor following an increase in network pressure, the T OFF timer is started:
at the end of this count, the system checks network pressure to establish whether another compressor is to be deactivated.
4.2.5 OPErAT. PArAMETErS MENU
This menu is used to make the configuration settings referring to the timings and operating pressure and timings that regulate
unload run and drainage of condensate.
>OPERAT. PARAMETERS
........
> Pressure
.....
> Timings
.........
> Operating press
Max: XXX bar
> Operating press
Min: XXX bar
unload run time
val: XXX min
Time Drain open
val: XXX min
Time Drain closed
val: XXX min