15
5.2
FUNCTIONING ECT-F
TOUCH
CONTROL
Introduction
The fridge is equipped with a latest generation Electronic Controller with a TFT display of 7”
Touch screen. This screen visualizes the temperature and the functioning status of the
equipment with an accuracy of 0,1°C. This instrument guarantees maximum safety in case of
alarms and failures, signaling promptly critical conditions and
recording
each event in order to
help the Service engineer to speed up the analysis and the repair of faulty conditions.
Safety is at the highest level by means of alarms for High and Low temperature, power
failure, open door as well as auto test to prevent failures. Safety is also assured in case of
faulty compressor relays or faulty defrost relays in order to prevent the freezing or
overheating of products.
The instrument records
every 30 Seconds
the equipment temperatures with a resolution
accuracy of 0,1°C.
Data are registered in two memories: the first is a flash memory able to store 1 year
operations; the second memory is represented by Secure Digital (SD) which works as a black
box since it can store up to 5 years of data.
In the display it is possible to charge data to build graphs from both memories.
The registered information in the SD is the following:
Day of the week, date and hour
Temperature chamber A and B (Chamber
– Evaporator - Condenser)
Temperature chamber A and B (Chamber A e Chamber B with DMLP TOUCH)
Product simulator temperature (only with DMLP TOUCH)
Programmed Setpoint
Status door chamber A and B (Opening
– Closed)
Duration door opening chamber A and B
Relay status to remote alarms (Dry contact)
Buffer battery tension (if present)
Presence/absence of the mains
Humidity probe temperature (if present)
High and Low alarms of temperature for both chambers and alarm delays (only with
DMLP TOUCH)
Alarm and failure codes
5.2.1
SWITCHING ON
Once connected the equipment to the mains, the display will show the “STAND-BY” page
which means that power is on.
Pressing the three red squares sequentially from left to right, the equipment will turn on.
Only at the first turning on of the equipment it is automatically requested to select language,
date and hour.
Figure 11