5.2.3
SET TEMPERATURE CHANGE
If the Control user password is enabled (Par
Errore. L'origine riferimento non è
stata trovata.
), user shall enter the password in order to switch off the system.
Touch in the homepage the Setpoint value in order to access to the dedicated page. Enter
the new value and press “OK”.
Together with the Setpoint, user can find also information about the compressor switching
on/off dif
ferential and of the Running setpoint (this differs from the “Current setpoint” when
the Night & Day function is active).
At every temperature change, user should always check that the set limits are
modified accordingly. If not, user should change them (see par. 5.2.4).
According to the stored products, the limits must be set some degrees higher and lower the
setpoint: the lower limit must always be 2°C or 3°C lower than the setpoint; whereas, the
upper limit must always be 2°C - 5°C more than the setpoint. For instance, for the storage of
drugs, user may set the setpoint at 8°C, lower limit at 6°C and upper limit at +11°C. For the
storage of blood at 4°C the limits must be set at +2°C and +6°C.
5.2.4
TEMPERATURE ALARM LIMITS CHANGE
If the Control user password is enabled (Par
Errore. L'origine riferimento non è
stata trovata.
), user shall enter the password in order to switch off the system.
Figure 14
Figure 15