background image

 

Page 4 of 6

 

 

T

OTAL

P

AC

2 Integrated Fire Protection System 

Cycling Wet Pipe Systems

 

 

 

FM-072G-0-143 E

 

batteries fail prior to the operation of the system, all alarms 
will be lost but the system will fail-safe and operate like a 
standard wet pipe system.  
The cycling function of the system will not operate in this 
condition, and the system must be manually shut-off.  
If power fails while the system is flowing water, the system 
will not cycle off and must also be manually shut-off. 

2. Emergency Instructions

 

(refer to piping diagram 

provided) 

To take system Out of Service: 

WARNING !  

Placing a control valve or detection system 

out of service may eliminate the Fire Protection 
capabilities of the system.  Prior to proceeding, notify all 
Authorities Having Jurisdiction.  Consideration should be 
given to employ a fire patrol in the affected areas. 

After a fire, verify that the fire is OUT and that placing the 

system out of service has been authorized by the 
appropriate Authority Having Jurisdiction. 

.1  Close Water Supply Control Valve 

(D1)

.2  Open system Main Drain Valve 

(D3)

 and inspectors test 

valve. Drain the system piping. 

.3  Silence alarms (refer to CONTROL PANEL SECTION 

for additional details).  

Note:  

Electric alarms controlled by a pressure switch 

(C2)

  

installed in the ½" (15mm) NPT connection for a Non-
interruptible Alarm Pressure Switch cannot be shut-off until 
the Flow Control Valve is reset or taken out of service. 

Sprinkler systems that have been subjected to a fire must 
be returned to service as soon as possible.  The entire 
system must be inspected for damage, and repaired or 
replaced as necessary. 
.4  Replace any detectors or sprinkler heads that have 

been damaged, or have been exposed to fire 
conditions. 

.5  Perform all maintenance procedures recommended in 

MAINTENANCE, describing individual components of 
the system that has operated. 

.6  Return the system to service as soon as possible.  

Refer to PLACING THE SYSTEM BACK IN SERVICE. 

3.  Placing the system back in service

  

(refer to TRIM SCHEMATIC) 

Note:  

For additional details, refer to instructions provided in 

the Viking Data Book describing the Flow Control Valve, 
and other system components. 

When the wet pipe system is ready to be placed in service, 
verify that all the equipment is adequately heated and 
protected to prevent freezing and physical damage. 

Note:  

For proper operation of the wet system and to 

minimize unwanted (false) alarms, it is important to remove 
trapped air from the system when filling it with water.  Air 
trapped in the system may also cause intermittent operation 
of the water motor gong during a sustained flow of water 
(such as the flow required by an open sprinkler or the 

system test valve).  Consider installation of auxiliary vents to 
facilitate venting. 

CAUTION:

  Opening of the water supply main control 

valve 

(A2)

 will result in water flow from any openings in 

the system.

 

1.  Slowly open the Emergency Release

 (B10)

 to allow the 

system pressure to return to normal. 

2.  Once the pressure has stabilized, close the Emergency 

Release

 (B10)

 and press the "System Reset" button on 

the Firecycle

® 

III Control Panel. 

 

Trouble conditions:

 

Inspections & Tests 

It is imperative that the system be inspected on a regular 
basis.  Refer to INSPECTIONS and TESTS recommended 
in current Viking technical Data describing individual 
components of the Viking Wet pipe System used. 
The frequency of the inspections may vary due to 
contaminated water supplies, corrosive or humid 
atmospheres as well as the condition of the air supply to the 
system.  In addition to the instructions herewith, local 
Authority Having Jurisdiction may have additional 
maintenance, testing and inspection requirements which 
must be followed. 

WARNING !  

Any system maintenance which involves 

placing a control valve or detection system out of service 
may eliminate the fire protection capabilities of that system.  
Prior to proceeding, notify all Authorities Having 
Jurisdiction.  Consideration should be given to employment 
of a fire patrol in the affected areas. 

Maintenance

 

Note:  

The owner is responsible for maintaining the fire 

protection system and devices in proper operating condition. 

For additional information, refer to MAINTENANCE 
INSTRUCTIONS provided in current Viking Technical Data 
describing individual components of the Viking Preaction 
System used.  
Where difficulty in performance is experienced, the valve 
manufacturer or his authorized representative shall be 
contacted if any field adjustment is to be made. 

The following requirements are based upon NFPA-25: 

Records. 

Records of inspections, tests, and maintenance of the 
system and its components shall be made available to the 
authority having jurisdiction upon request. Typical records 
include, but are not limited to, valve inspections; flow, drain, 
and pump tests; and trip tests of Flow Control valves. 
Acceptance test records should be retained for the life of the 
system or its special components. Subsequent test records 
should be retained for a period of 1 year after the next test. 

Summary of Contents for TOTALPAC2

Page 1: ...intaining the fire protection system and devices in proper operating condition Refer to CONFIGURATION DESCRIPTION for maintenance instructions 4 General Description There are various types of wet pipe systems all of them using closed automatic sprinklers in the sprinkler piping This TOTALPAC2 integrated fire protection system by FireFlex Systems Inc consists of a cycling wet pipe system trim total...

Page 2: ...s been satisfied Should the fire rekindle the Firecycle III will initiate the sequence again This unique cycling feature will repeat as long as power is available to the panel helping to minimize water usage water damage and the danger of pollution to surrounding areas Firecycle III systems are also Fail Safe Note TOTALPAC2 Firecycle III Systems are available with electrical type release and the i...

Page 3: ...ivates latching normally open solenoid valve F1 closed Water discharges until all Firecycle Detectors have reset cooled below their set point After all detectors have reset the control panel activates the Soak Timer allowing the system to continue discharging water for a preset time period When the Soaking Timer has expired the control panel de energizes normally closed Release Solenoid Valve F2 a...

Page 4: ...larms it is important to remove trapped air from the system when filling it with water Air trapped in the system may also cause intermittent operation of the water motor gong during a sustained flow of water such as the flow required by an open sprinkler or the system test valve Consider installation of auxiliary vents to facilitate venting CAUTION Opening of the water supply main control valve A2...

Page 5: ...on Main Drain Test Riser Flow Test to determine if change in water supply or control valve position Test procedure Record the pressure indicated by the supply water gauge Fully open the main drain valve Record residual pressure Close the main drain valve slowly Record the time taken for supply water pressure to return to the original pressure Open the alarm control valve Semi Annually Valve superv...

Page 6: ...Page 6 of 6 TOTALPAC2 Integrated Fire Protection System Cycling Wet Pipe Systems FM 072G 0 143 E ...

Reviews: