DF-52095 06/18/04 Page 1 of 2
GENERAL
GENERAL
GENERAL
GENERAL
GENERAL
The
MicroScan-2410B
is a 24-volt, ten-zone, Style B (Class
B), Conventional Fire Alarm Control Panel. Designed ex-
clusively to meet the latest fire alarm market requirements,
the highly cost-effective MS-2410B can be used in a vari-
ety of low- to mid-sized applications, including: Local, Aux-
iliary, Remote Station, and Proprietary Fire Alarm System.
Provides supervised reverse polarity protection when us-
ing a 4XTMF Transmitter Module.
FEA
FEA
FEA
FEA
FEATURES
TURES
TURES
TURES
TURES
Ten Style B (Class B) Initiating Device Circuits (IDCs).
Zones 1 - 10 accept two-wire smoke detectors and
any normally-open contact devices.
Zones 1 - 8 configured as general alarm zones.
Zones 9 and 10 programmable as smoke zones or
supervisory alarm zones.
Two built-in, Style Y (Class B) Notification Appliance
(Bell) Circuits (NACs).
NACs may be programmed:
Silenceable.
Non-Silenceable.
Auto-Silence (program 5 to 20 minutes).
2.5 amps of NAC power, expandable to 5.0 amps.
3.6 amps of total system power expandable to 6.6 amps.
24 VDC operation.
Supervised reverse polarity protection
(using 4XTMF).
Resettable four-wire smoke detector power @ 300 mA.
Non-resettable power @ 500 mA.
Integral battery charger capable of charging up to 18 AH
batteries (batteries over 12 AH require use of the
FireLite
BB-17F
battery backbox).
Alarm, Trouble and Supervisory, Form-C relays standard.
Fuseless, power-limited technology meets all the lat-
est power-limiting requirements.
Fully programmable via built-in keypad.
Program mode password and cabinet security key pre-
vent unauthorized access to ensure the integrity of the
field program information.
Programmable Alarm Verification (zones 1 through 3 with
two-wire smoke detectors only).
Last Event Recall feature traps unverified alarms or in-
termittent troubles.
One-man walk-test programmable for silent or audible
test.
Disable/Enable control per IDC (zones).
Programmable Trouble Reminder and Silence Inhibit
capability.
Slide-in labels for zone identification and programming
options.
Electronics and operational controls fully enclosed in lock-
able cabinet capable of housing up to 12 AH batteries.
Optional flush mount trim ring (TR-4-R).
Optional dead-front dress panel (
DP-2410B
).
RTB
Remote Trouble Buzzer option.
Optional
LED-10IM
interface module provides EIA-485,
two-wire, serial output for:
Relay-by-zone capability with optional
ACM-8RF
.
Optional
LED-10 Series
Remote Fire Annunciators.
Optional
AFM Series
LED Annunciators.
LDM Series
Graphic Annunciator Drivers.
Local energy or remote station connection with optional
4XTMF
transmitter module.
SPECIFICA
SPECIFICA
SPECIFICA
SPECIFICA
SPECIFICATIONS
TIONS
TIONS
TIONS
TIONS
120 VAC, 60 Hz, 2.3 amps.
Wire size:
minimum 14 AWG (2.0 mm²) with 600-volt
insulation.
Total 24 VDC system power:
3.6 amps (expandable to
6.6 amps).
Notification appliance (bell) circuit (NAC) power:
2.5
amps (expandable to 5.0 amps).
Maximum current per NAC:
1.25 amps (expandable to
2.5 amps).
S624
MicroScan-2410B
MicroScan-2410B
MicroScan-2410B
MicroScan-2410B
MicroScan-2410B
10-Zone, Class B
10-Zone, Class B
10-Zone, Class B
10-Zone, Class B
10-Zone, Class B
Fire Alarm Control Panel
Fire Alarm Control Panel
Fire Alarm Control Panel
Fire Alarm Control Panel
Fire Alarm Control Panel
DF-52095 A2-425
June 18, 2004
Section: Conventional
www.firelite.com
MEA
299-00-E
This document is not intended to be used for installation purposes. We try to
keep our product information up-to-date and accurate. We cannot cover all
specific applications or anticipate all requirements. All specifications are sub-
ject to change without notice. For more information, contact
FireLite
Alarms
, One Fire-Lite Place, Northford, Connecticut 06472. Phone: (800) 627-
3473, Toll-Free FAX: (877) 699-4105.
Made in the U.S.A.
7165-0075:188
California
State Fire
Marshal
firealarmresources.com