Page 2 of 2 DF-52095 06/18/04
Maximum battery charging capability:
18 AH.
Initiating Device Circuits (zones)
Initiating Device Circuits (zones)
Initiating Device Circuits (zones)
Initiating Device Circuits (zones)
Initiating Device Circuits (zones)
Ten Style B (Class B).
Zones may be programmed for:
Two-wire smoke detectors and any normally open
contact device.
Zones 1 - 8 configured as general alarm zones only.
Zones 9 and 10 can be configured as smoke zones
or supervisory alarm zones.
All circuits are power-limited and supervised, meeting
the latest requirements using fuseless technology.
Notification Appliance (Bell) Circuits
Notification Appliance (Bell) Circuits
Notification Appliance (Bell) Circuits
Notification Appliance (Bell) Circuits
Notification Appliance (Bell) Circuits
(NACs)
(NACs)
(NACs)
(NACs)
(NACs)
Two Style Y (Class B) @ 1.25 amps (expandable to 2.5
amps) each.
NACs may be programmed:
Silenceable.
Non-Silenceable.
Auto-Silence (program 5 to 20 minutes).
All circuits are power-limited and supervised, meeting
the latest requirements using fuseless technology.
Auxiliary Outputs
Auxiliary Outputs
Auxiliary Outputs
Auxiliary Outputs
Auxiliary Outputs
Resettable four-wire smoke detector power @ 300 mA.
Non-resettable power @ 500 mA.
NOTE:
Total current for auxiliary power outputs and two NACs
must not exceed 6.0 amps. Total system current in excess of 3.6
amps requires the optional XRM-24 transformer and 12 or 18 AH
batteries.
Integral Form-C Alarm, Trouble and Supervisory relays,
rated at: 2.0 amps @ 30 VDC (resistive), 2.0 amps @ 30
VAC (resistive).
EIA-485 Port, Compatible Devices
EIA-485 Port, Compatible Devices
EIA-485 Port, Compatible Devices
EIA-485 Port, Compatible Devices
EIA-485 Port, Compatible Devices
LED-10IM:
EIA-485 Interface Module. Provides MS-
2410B with EIA-485 output, capable of supporting up to 10
compatible EIA-485 devices.
LED-10 Series:
LED-type fire annunciators capable of
displaying Alarm (red) and Trouble (yellow) LEDs for all
ten Initiating Device Circuits (IDCs).
AFM Series:
LED-type fire annunciators capable of pro-
viding up to 16 zones of Alarm (red) annunciation and com-
mon system trouble LED. Mount to 4-gang electrical box
ONLY
.
LDM Series:
Lamp Driver Module series for use with
custom graphic annunciators.
ACM-8RF:
Remote Form-C relay module. Provides eight
mappable Form-C relays driven by EIA-485 for relay-by-
zone capability (two minimum required for relay-by-zone).
Each requires ABS-8RF for mounting.
NOTE:
For more detailed information on
Compatible EIA-485
Devices
for use with the MS-2410B, please refer to the
LED-10,
AFM/AFM-X, LDM
or
ACM-8RF
data sheets, document numbers
DF-51500, DF-51465, DF-51384, and DF-51555 respectively.
Cabinet Specifications
Cabinet Specifications
Cabinet Specifications
Cabinet Specifications
Cabinet Specifications
See diagrams below.
PRODUCT LINE INFORMA
PRODUCT LINE INFORMA
PRODUCT LINE INFORMA
PRODUCT LINE INFORMA
PRODUCT LINE INFORMATION
TION
TION
TION
TION
MS-2410B
24-Volt, 10-zone, Class B, FACP.
XRM-24
120VAC, 100 VA transformer. Expands total
system power from 3.6 amps to 6.6 amps.
RTB
Remote Trouble Buzzer.
4XTMF
Remote station output or municipal box con-
nection (reverse polarity application).
LED-10IM
EIA-485 port interface module.
Required for
use with EIA-485 compatible devices
(see
above)
.
DP-2410B
Optional internal dead-front dress panel.
TR-4-R
Flush mount trim ring.
BB-17F
UL listed battery backbox.
Required for use
with batteries over 12 AH.
ABS-8RF
Metal enclosure for mounting each ACM-8RF
module.
2410RB
Replacement motherboard.
BAT-12120
Battery, 12 volt, 12.0 AH
(two required).
BAT-12180
Battery, 12 volt, 18.0 AH
(two required; requires
BB-17F battery backbox for mounting).
52095box.wmf