MS-4424 15153:F1 06/18/97
23
Transmitter Module -- 4XTMF
Polarities shown in activated positions. The wiring of this module must follow the requirements as
specified in the
"General" Section, "UL Power Limited Wiring Requirements."
Push the disconnect switch down to prevent unwanted activation of the Municipal Box during testing of the
control panel. The Disconnect LED will remain illuminated while the Municipal Box is disconnected. The
System Trouble LED will indicate disconnected and/or Open Circuit conditions on the Municipal Box.
Cutting the TBL jumper will allow the alarm reverse polarity circuit to open on trouble, if no alarm exists.
Note:
Remote Alarm, Remote Trouble and Municipal Box wiring can leave the building.
+
-
+
-
+
-
Remote Alarm
Remote Trouble
}
TBL Jumper
Disconnect
LED
Disconnect
Switch
}
}
}
}
Power Limited Circuit
Non-Power Limited Circuit
No Connection
Municipal Box *
* Dummy load terminals 6 and 7 (4.7K, 1/4 W
resistor) if Municipal Box is not connected.
1
2
3
4
5
6
7