1 2 3 4 5 6
O
N
To set a switch to the "ON" position,
slide it up.
Micro Fail LED
Battery Fail
LED
Ground Fault LED
3.7
Dip Switch Location and Descriptions
Switch 1: Alarm Verification
If selected, alarm signals that occur on any
zone will be subjected to a two-minute verifica-
tion period to determine if the alarm is true.
Note that the control panel will distinguish if the
alarm signal came from a shorting-type contact
device (manual pull station, 4 wire detector, or
heat detector) or a two-wire smoke detector,
and will not employ verification of alarm signals
from the contact devices.
Switch 3: Supervisory on Zone 4
If set for Supervisory, Initiating Device Circuit 4
will function as a supervisory circuit. Activation
of a tamper or other supervisory switch on this
circuit will not result in an alarm condition. The
piezo will sound a distinct pulsing tone and the
yellow LED on zone 4 will flash along with the
supervisory LED. (See Section
"Output Cir-
cuits" for Jumper Configuration Table.)
Switch 2: Waterflow on Zone 3
If set, Initiating Device Circuit 3 will function as
a non-silenceable circuit. If an alarm occurs on
this zone, the ALARM SILENCE switch will not
silence any activated output circuits.
Note: The Reset key must be depressed after any switch configuration has been made.
Switch 4: Silence Inhibit
If selected and an alarm occurs, the ALARM
SILENCE switch will not function until 60
seconds have passed since initiation of the
alarm. If another alarm occurs, the timer
will restart at 60 seconds.
Switch 5: Disable Bells
When this switch is set "ON", the four
Notification Appliance Circuits and the
SYSTEM ALARM relay will be disabled,
and a local trouble signal will be generated.
Switch 6: One Man Walk Test
Setting this switch to the "ON" position
places the control panel in Walk Test Mode.
The first alarm on the Initiating Device
Circuit under test will ring associated Noti-
fication Appliance Circuit(s) for 5 seconds.
Zone Alarm LED will flash. The second
alarm on Initiating Device Circuit under test
will ring associated Notification Appliance
Circuit(s) for 1 second. Zone Alarm LED
will illuminate steadily. A Trouble condition
on Initiating Device Circuit under test will
sound piezo and light Zone Trouble LED.