MS-4424 15153:F1 06/18/97
29
MS-4424 Control Panel containing the main control board, cabinet (backbox and door), main supply
transformer and power supply.
Batteries (refer to Appendix A for Standby Power Requirements).
Initiating Devices - connected to one of the control panel's Initiating Device Circuits.
Notification Appliances - connected to one of the control panel's Notification Appliance Circuits.
The following additional equipment is needed for compliance with the NFPA standards listed below:
NFPA 72-1993 Fire Alarm Systems for Central Station Service (Protected Premises Unit)
NOTI-FIRE 911A/911AC DACT* or MS-5012 - for connection to a compatible listed Central Station DACR
or Protected Premises Receiving Unit. This unit must be installed as outlined in Figure B-1A or B-1B.
NFPA 72-1993 Auxiliary Fire Alarm Systems
4XTMF Transmitter Module for connection to a compatible listed Local Energy Municipal Box. This unit
must be installed as outlined in Figure B-2.
NFPA 72-1993 Remote Station Fire Alarm Systems
4XTMF Transmitter Module for connection to the Fire•Lite RS82-9 Remote Station Receiver. See Figure
B-3 for installation instructions for this unit
OR
NOTI-FIRE 911A/911AC DACT * or MS-5012 - for connection to a compatible listed remote station DACR.
This unit must be installed as outlined in Figure B-1A/B.
NFPA 72-1993 Proprietary Fire Alarm Systems
Potter EFT-C McCulloh Transmitter.* See Figure B-4 for installation instructions for this unit .
* Applications which require the NOTI-FIRE 911A/911AC or the Potter EFT-C are not FM approved.
Appendix B: NFPA Standard-Specific Requirements
The Fire•Lite MS-4424 has been designed for use in commercial, industrial, and institutional applications
and meets the requirements for service under the National Fire Protection Association (NFPA) Standards
outlined in this appendix. The minimum system components required for compliance with the appropriate
NFPA standard are listed below.