MS-4424 15153:F1 06/18/97
33
6
7
Figure B-2: NFPA 72-1993 Auxiliary Fire Alarm Systems
All connections are power limited and supervised. This application is not suitable for separate transmission
of sprinkler supervisory or trouble conditions.
Note: Maximum loop resistance allowed for wiring from control panel to Municipal Box is 3 ohms.
4XTMF
Transmitter Module
(activated polarities shown)
+
-
Municipal Box Circuit
Gamewell
Model M34-56
Local Energy
Municipal Box
+
-
Note:
Municipal Box wiring can leave the building.