MS-4424 15153:F1 06/18/97
8
1.5
Optional Meters
Voltage, Current Meters (4XMMF)
The Meter Module provides a voltmeter to measure the voltage across the
batteries and an ammeter to measure the charging current to the batteries. The
meters are provided as an assembly that mounts to the lower left-hand corner
of the cabinet.
LED Interface Module (4XLMF)
Maximum voltage/current, each output: 27.6V/8mA.
Note: Outputs are power limited.
Zone Relay Module (4XZMF)
Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive).
Transmitter Module (4XTMF)
For Local Energy Municipal Box service (NFPA 72-1993 Auxiliary Fire Alarm Systems)
Supervisory current: 5.0 mA.
Trip current: 0.35 amps (subtracted from Notification Appliance power).
Coil Voltage: 3.65 VDC.
Coil resistance: 14.6 ohms.
Maximum allowable wire resistance between panel and trip coil: 3 ohms.
Municipal Box wiring can leave the building.
For Remote Station service (NFPA 72-1993 Remote Station Fire Alarm Systems):
Maximum load for each circuit: 10 mA.
Reverse polarity output voltage: 24 VDC.
Remote Alarm and Remote Trouble wiring can leave the building.
1.4
Remote Annunciator
Remote Annunciator (RZA-4XF)
The Remote Annunciator mounts on a standard single-gang box, and provides LED
indication of the following:
• Alarm Zone 1 (red)
• Alarm Zone 2 (red)
• Alarm Zone 3 (red)
• Alarm Zone 4 (red)
• System Trouble LED (yellow)
A Local Trouble Sounder and Silence Switch are also provided. All LED wiring is
supervised for open conditions. Any open condition will cause the System Trouble
LED to illuminate. Slide-in paper labels permit an easy change of zone information.
Note: The Remote Annunciator requires the use of an LED Interface module (4XLMF)
Technical Manuals Online! - http://www.tech-man.com