15465 Rev F 5/2/97 P/N 15465:F
19
When a supervisory condition occurs, the control panel will:
✔
Turn on the supervisory LED.
✔
Activate the supervisory relay driver. (TB3-6)
✔
Display the following message: (
5UP4
).
✔
Communicate the supervisory condition to the central station.
✔
Store "supervisory" message in History file.
✔
Pulse the piezo sounder at 0.5 sec on 0.5 sec off rate.
When the supervisory condition has been cleared (condition is restored and
the reset switch has been pressed) the MS-5012 will perform the following:
✔
Turn off the supervisory LED .
✔
Deactivate the supervisory relay driver. (TB3-6)
✔
Clear the display of the SUP4 message .
✔
Communicate the "supervisory restoral" message to the central station.
✔
Shut off the piezo sounder.
Trouble Conditions
The control panel will perform the following upon detection of a trouble
condition:
✔
Turn on the trouble LED.
✔
Activate the trouble relay driver. (TB3-5)
✔
The appropriate trouble message will be displayed. Below are the
trouble messages shown in priority fashion from the highest priority
to the lowest:
AC
F 1
F 3
F 2
F 5
F 4
F E
L b
no b
no 1
no 2
bELL
PH 1
PH 2
F A
rES
AC Loss (Must press up, down, or first event to view)
Trouble on zone 1
Trouble on zone 3
Trouble on zone 2
Trouble on zone 5
Trouble on zone 4
Ground fault
Low battery
No battery
Primary Phone Line Fault
Secondary Phone Line Fault
Bell circuit fault
Primary Number Communication Fault
Secondary Number Communications Fault
Annunciator Fault
Reset