15465 Rev F 5/2/97 P/N 15465:F
21
Two phone numbers must be programmed (see Section 4.0), the primary
phone number and the secondary phone number. All system reports will
be transmitted to the primary phone number. Reports will automatically
be sent to the secondary phone number if attempts to transmit to the
primary phone number are unsuccessful. If 10 attempts to communicate
are unsuccessful, the Communicator Failure output will be turned on
(TB3, terminal 7). Note that as an option, all reports may be sent to the
secondary phone number.
The MS-5012 meets NFPA 72-1993 for Central Station Signaling
Service and for Remote Station Protective Signaling Service reporting
requirements for: (a) the type of signal (b) condition (c) location of the
reporting premises. The general priority reporting structure is:
1. Zone Alarms and Restores
2. Zone Troubles and Restores
3. System Troubles and Restores
4. 24-hour test
The control panel is capable of reporting detailed messages depending
upon the format in use. Tables 4.3-1 through 4.3-4 list these messages.
The table below shows the reporting structure for all of the tone burst
type formats.
Table 2.4-1: Format Selection Addresses (16+42)
Format #
2, 4, 6, 8
Format #
3, 5, 7, 9
Format #
A, C
Format #
B, D
Report
3+1/4+1 Standard
3+1/4+1/ Expanded
4+2/Standard
4+2/Expanded
Alarm
SSS(S) A
SSS(S) A
AAA(A) Z
SSSS AA2
SSSS AZ
Alarm Restore
SSS(S) RA
SSS(S) RA
RARARA(RA) Z
SSSS RARA2
SSSS RAZ
Zone Trouble
(Zone Open)
SSS(S) TZ
SSS(S) TZ
SSSS TZTZ2
SSSS TZZ
Zone Trouble
Restore
SSS(S) RTZ
SSS(S) RTZ
RTZRTZRTZ(RTZ)Z
SSSS RTZRTZ2
SSSSRTZZ
System Trouble
SSS(S) TS
SSS(S) TS
TSTSTS(TS) Y
SSSS TSTS2
SSSS TSY
System Trouble
Restore
SSS(S) RTS
SSS(S) RTS
RTSRTSRTS(RTS) Y
SSSS RTSRTS2
SSSS RTSY
Low Battery
SSS(S) L
SSS(S) L
SSSS LL2
SSSS LL2
Low Battery
Restore
SSS(S) RL
SS(S) RL
SSSS RLRL2
SSSS RLRL2
AC Loss
SSS(S) P
SSS(S) P
SSSS PP2
SSSS PP2
AC Loss Restore
SSS(S) RP
SSS(S) RP
SSSS RPRP2
SSSS RPRP2
Supervisory
Condition
SSS(S) V
SSS(S) V
VVV(V) Z
SSSS VV2
SSSS VV2
Supervisory
Condition
Restore
SSS(S) RV
SSS(S) RV
RVRVRV(RV) Z
SSSS RVRV2
SSSS RVZ
Test Reprot
SSS(S) X
SSS(S) X
SSSS XX2
SSSS XX2