15465 Rev F 5/2/97 P/N 15465:F
22
Where:
SSS 0r
SSSS
= Subscriber ID
A
= Alarm (1st digit)
A2
= Alarm (2nd digit)
Z
= Zone Number
RA
= Alarm Restore (1st digit)
RA2
= Alarm Restore (2nd digit)
TZ
= Zone Trouble (1st digit)
TZ2
= Zone Trouble (2nd digit)
RTZ
= Zone Trouble Restore (1st digit)
RTZ2
= Zone Trouble Restore (2nd digit)
TS
= System Trouble (1st digit)
TS2
= System Trouble (2nd digit)
RTS
= System Trouble Restore (1st digit)
RTS2
= System Trouble Restore (2nd digit)
L
= Low Battery (1st digit)
L2
= Low Battery (2nd digit)
RL
= Low Battery Restore (1st digit)
RL2
= Low Battery Restore (2nd digit)
P
= AC Loss (1st digit)
P2
= AC Loss (2nd digit)
RP
= AC Loss Restore (1st digit)
RP2
= AC Loss Restore ( 2nd digit)
V
= Supervisory Condition (1st digit)
V2
= Supervisory Condition (2nd digit)
RV
= Supervisory Condition Restore (1st digit)
RV2
= Supervisory Condition Restore (2nd digit)
X
= Test Report (1st digit)
X2
= Test Report (2nd digit)
Y
= 6 = AC Loss
= 7 = Ground Fault
= 8 = Low Battery
= 9 = No Battery
= A = Telco Primary Line Fault
= B = Telco Secondary Line Fault
= C = Main Bell Fault, Annunciator Fault
= D = Communication Fault to Primary Number
= E = Communication Fault to Secondary Number
= F = System Off Normal Fault/System Fault (Slave Operation,
See Section 6.0)
Note: For Expanded Reporting, the control panel automatically adds the digit
corresponding to the zone number, and the second digit corresponding to any
system trouble condition. Only the first digit is programmable.