15465 Rev F 5/2/97 P/N 15465:F
34
ADM-12 Annunciator Driver Module
The Annunciator Driver Module supports
the RZA-5F Remote Annunciator module.
Annunciator wiring is supervised for open
conditions by this module. The Annunciator
Driver Module mounts to the main board,
occupying one of the two option connectors.
(See Section 1.6)
3.7 Optional
Boards
The RZA-5F Remote Annunciator mounts on a standard single-gang
box, and provides LED indication of the following:
Alarm Zone 1 (red)
Alarm Zone 2 (red)
Alarm Zone 3 (red)
Alarm Zone 4 (red)
Alarm Zone 5 (red)
System Trouble (yellow)
The remote annunciator provides
individual zone alarm LEDs, a
system trouble LED, a piezo
sounder and a remote sounder shut
off switch.
A Local Trouble Sounder and
Silence Switch are also provided.
All LED wiring is supervised for
open conditions. Any open
condition will cause the System
Trouble LED to illuminate.
NOTE: The Remote Annunciator requires the use of an ADM-12
Annunciator Driver Module.