4.0 Programming Instructions
Note that as you enter
information into the
control panel, the digits
will scroll across the
display from right to left
Programming of the MS-5012 is possible at any time except when an
alarm condition is present in the Normal Mode of operation.
The MS-5012 has been designed for many different types of applications.
After examining your specific application, review the programming
options and choose the entries best suited for your system.
The MS-5012 has a built-in programmer. All programming selections are
stored in nonvolatile Electrically-Erasable Programmable Read-Only
Memory (EEPROM). This ensures that the control panel will remember all
entries made in programming mode even if both AC and battery power are
removed.
The user must program the primary and secondary phone numbers,
account numbers and 24 hour test report times for each Central Station
account and the current time. The control panel comes with factory chosen
options/features already programmed. Other options/features may be
programmed if desired. If all factory default settings are acceptable,
programming is complete.
To enter the Program Mode, press the
w
key once, (the display will go
blank) you then have ten seconds to start entering the code (
7764
) .
☛
7764
spells PROG on a Touch-Tone® phone
If an incorrect key is entered, just reenter the proper 4-digit code before
hitting the
t
key
7
77
776
7764
You are allowed a pause of up to 10 seconds in between each number
while entering the code. The control panel will then be in Program Mode
and show the display
00 F
. You are allowed up to ten minutes of idle
time at this point before starting your programming, otherwise the control
panel will go back to Normal Mode. You also have a maximum of 10
minutes between any key stroke.
Programming
Mode
4.1 Entering
Program Mode