15465 Rev F 5/2/97 P/N 15465:F
41
Programming the Primary Number Account Code (17-20) takes up
four locations at addresses 17-20. The defaults are all "0"s.
17
0
Valid entries are (0-9 and A-F). The number of digits entered must
match the format selection. If programming "2, 3, 4, or 5" into address
16, enter 3 digits. (location 20 is ignored) If programming "6, 7, 8, 9, A,
B, C, or D" into address 16, enter 4 digits.
Programming the Primary Number 24 Hour Test Time (21-24).
Use military time when entering the 24 hour "test" time. The 24 hour
test time over phone number 1 to the central station takes up four
locations, from addresses 21-24. The default is 00:00 (12:00 midnight).
The limits for each location are as follows: 21: enter 0, 1, 2; 22: enter
0-9; 23 : enter 0-5; 24: enter 0-9. Note: Do not use A-F.
Programming Primary Number 24/12 Hour Test Time (25). The test
message sent to the Primary phone number may be sent every 12 or 24
hours. If the message is to be sent every 24 hours, leave the factory
default entry of zero. If 12 hour test reports are needed, enter a "1" into
this address.
Programming the Secondary Phone Number (26-41) is similar to the
primary phone number located in addresses 00 - 15. The defaults are
also all "F"s.
4 8 4 7 1 6 1 F F F F F F F F F
26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 .
Programming Secondary Number Communication Format (42) is
programmed the same way as the primary number's Comm Format in
address 16. Default entry is "A" 4+2 Standard. Choose one entry from
the list below:
0: Not Used
1: Not Used
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK --- Table 4.3-3
3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK -- Table 4.3-3
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK --- Table 4.3-3
5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK--- Table 4.3-3
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK --- Table 4.3-3
7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK -- Table 4.3-3
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK --- Table 4.3-3
9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK - Table 4.3-3
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK -- Table 4.3-4
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK - Table 4.3-3
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK -- Table 4.3-4
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK - Table 4.3-3
E: Not Used
F: Not Used