15465 Rev F 5/2/97 P/N 15465:F
44
Secondary Number Account Code (43-46) is programmed in
addresses 43 - 46 in the same manner as the primary phone number
Account Code. Default entries are all "0's."
Secondary Number 24-Hour Test Time (47-50) is programmed in
addresses 47-50 in the same manner as the primary number 24-Hour
Test Time. Default is 00:00 (12:00 midnight).
Secondary Number 24/12 Hour Test Time (51) The test message sent
to the Secondary phone number may be sent every 12 or 24 hours. If the
message is to be sent every 24 hours, leave the factory default entry of
zero. If 12 hour test reports are needed, enter a "1" into this address.
Programming Zone 3 Functionality (52)
The following entries may be selected: 0 = non silenceable Waterflow
Zone, 1 = N.O. contact device zone or silenceable Waterflow zone, 2 =
2-Wire detector device zone. If "0" is entered, address 53-54 must be
programmed if a delay is needed. Selecting a "1" entry allows any
Normally Open contact device to be connected on this zone. Selecting a
"2" entry allows for 2-wire detectors to be connected on this zone.
(Style B only) Factory setting is "0," non silenceable Waterflow zone.
Programming Waterflow Retard Timer (53-54) This field allows you
to select a delay of up to 89 seconds for declaring a "Waterflow Alarm."
Factory default is one second. The default for addresses 53 and 54 are
"00" (no additional delay). Valid keys for 53 are 0-8, and 0-9 for 54.
Program an entry into this address only if selecting a "0" in address 52
above. Be careful to include any built in delays of the waterflow device.
Programming AC Loss Reporting Delay (55) Enter a digit of 1, 2, 3,
4, 5, or 6 corresponding to the number of hours to be delayed in
reporting loss of AC power. Factory default is 6-hour delay. 0=6 hours,
1=7 hours, 2=8 hours, 3=9, 4=10, 5=11, and 6=12.
Slave Communicator/Fire Panel Selection (56)
Leaving address 56 at "0" means the MS-5012 is operating as a fire
panel only. Selecting "1" will make it operate as a slave communicator
only. See Section 6, Slave Communicator Configuration. Selecting "2"
will make it operate as a Fire panel/communicator.
For Addresses 57 - 67 leave the location programmed at "0" to accept
the factory default, or set the location to "1" to change it.
Secondary Phone Number (57) Leaving address 57 at "0" means that
reports will be transmitted to the secondary number only if calls to the
primary number are unsuccessful. Programming a "1" causes all reports
to be transmitted to the secondary number.