15465 Rev F 5/2/97 P/N 15465:F
45
Alarm Verification on Detector Zones 2 and 3 (58) Factory Default
setting for this address is "0" which means no alarm verification.
Entering a "1" enables verification for zone 2 and zone 3. Consult
local Authority Having Jurisdiction (AHJ) prior to altering this
address.
Alarm verification works only on zones programmed as 2-wire
detector zones. After detecting an alarm, the panel removes power
from all zones for 6 seconds, resetting all 2-wire smoke detectors.
Power is reapplied and a 12 second retard period allows detectors to
stabilize. During the retard/reset period of 18 seconds, subsequent
alarms by the same initiating zone are ignored. An alarm detected on
any other 2-wire detector zone during the retard period will cause
immediate verified alarms. A subsequent alarm on the initiating zone
occurring within the confirmation time will cause a verified alarm.
Note: Mixing devices on zones designated as 2-wire smoke zones is not
recommended.
During the alarm verification period, access to other modes of
operation is prevented.
Note: Consult local Authority Having Jurisdiction (AHJ) prior to
altering addresses 59, 60, 61 and 62.
Silence Inhibit (59) The factory default "0" disables the silence inhibit
feature. A "1" selects the following function: Silencing of the
Notification Appliance Circuit and piezo is prohibited for 1 minute.
Auto Silence (60) For address 60, you may leave the default at "0" to
allow the Notification Appliance Circuit to remain on until it's reset, or
select "1" to automatically silence the Notification Appliance Circuit
after 10 minutes.
Trouble Reminder (61) Factory default "0" disables the trouble
reminder feature. Selecting "1" will cause a reminding "beep" every 15
seconds during an alarm (after the silence switch is pressed) and
"beep" every two minutes during a trouble condition. The "beeps" from
the on board sounder will occur until the alarm or fault is cleared.
Bell Disable (62) For location 62, choosing default "0" means the
Notification Appliance Circuit is enabled. Setting the address to "1,"
causes the bell to be disabled during an alarm. Entering a "1" causes
the Trouble LED to remain on and bell fault message sent to the
Central Station(s).