15465 Rev F 5/2/97 P/N 15465:F
53
Programming Reference Sheet
--- To enter Programming, press Mode: 7 7 6 4, Enter
❑
00
❑
01
❑
02
❑
03
❑
04
❑
05
❑
06
❑
07
❑
08
❑
09
❑
10
❑
11
❑
12
❑
13
❑
14
❑
15
Addresses 00 to 15 store the Primary Phone Number. Enter "F" to represent the end of the number.
❑
16
Primary Comm Format:
Enter 0 - F.
❑
17
❑
18
❑
19
❑
20
Primary Account Code: Valid keys are 0-F.
❑
21
❑
22
❑
23
❑
24
Primary 24-Hour Test Time.
Enter military time (i.e. 1400 for 2 PM)
❑
25
Primary 24/12 Hour Test Time. Enter "1" for 12 hour; "0" for 24 hour.
❑
26
❑
27
❑
28
❑
29
❑
30
❑
31
❑
32
❑
33
❑
34
❑
35
❑
36
❑
37
❑
38
❑
39
❑
40
❑
41
Addresses 26-41 store the Secondary Phone Number.
Enter "F" to represent the end of the number.
❑
42
Secondary Comm Format: Enter 0-F.
❑
43
❑
44
❑
45
❑
46
Secondary Account Code: Valid keys are 0-F.
❑
47
❑
48
❑
49
❑
50
Secondary 24-Hour Test Time. Enter military time (i.e. 1400 for 2 pm)
❑
51
Secondary 24/12 Hour Test Time. Enter "1" for 12 hour; "0" for 24 hour.
❑
52
Zone 3 Function Select
(0 = Waterflow, 1 = N.O. contact devices, 2 = 2-Wire detectors)
❑
53
❑
54
Waterflow Reporting Delays. Valid keys for field 53 are 0-8, and 0-9 for field 54.
❑
55
AC Loss.
Enter number of hours to delay reporting of AC loss. (0=6 hours, 1=7 hours ...6=12 hours)
❑
56
Slave Comm Selection.
"0" for panel only; set to "1" for slave operation; "2" for fire control/comm opera-
tion
❑
57
Secondary Phone Number.
Enter "0" for secondary as a backup; "1" to transmit always.
❑
58
Alarm Verify.
Enter "0" for no verification; "1" for verification.
❑
59
Silence Inhibit.
Enter "0" to disable silence inhibit; "1" to enable.
❑
60
Auto Silence.
Enter "1" to silence notification appliances 10 minutes after activation.
❑
61
Trouble Reminder.
Enter "1" to enable reminder beep (alarm-every 15 seconds; trouble-every 2 minutes.)
❑
62
Bell Disable.
Enter "1" to disable the panels Notification Appliance Circuit.
❑
63
Annunciator Present.
Enter "1" if an annunciator is wired to the system.
❑
64
Zone 4 Function Select.
Enter "0" for supervisory service; "1" for N.O. contact devices.
❑
65
Not used.
❑
66
Touchtone Rotary Select.
Enter "0" for touchtone dialing, "1" for rotary.
❑
67
Make Break Ratio.
Enter "0" for 67/33 make/break ratio; "1" for 62/138.