Split Temporal Mode of Operation
Applications
FCPS-24FS PN 51883:B 12/04/02
31
Notes: The following notes apply to Figure 5.3 on page 30.
1. When the FCPS-24FS power supply is in an inactive state (control module not
active), a trouble on the power supply will result in an open circuit condition on
the control module output circuit (monitored by End-of-Line Resistor across
Terminals 5 & 6). As an alternative, the trouble contacts at TB5 of the power
supply can also be used for independent trouble monitoring.
2. Do not loop wires under screw terminals. Break wires to maintain proper
supervision.
3. An End-of-Line Resistor must be installed between terminals 5 & 6 for control
module wiring supervision (the ELR value is dependent on the module
employed) and across terminals 7 & 8 for FACP NAC wiring supervision (the
ELR value is dependent on the NAC).
4. For a list of compatible devices, refer to the Device Compatibility Document.