Applications
Remote Supply With Resettable and Nonresettable Power
32
FCPS-24FS PN 51883:B 12/04/02
5.4 Remote Supply With Resettable and Nonresettable Power
The FCPS-24FS can be used as a remote stand-alone power supply to provide power to
any devices that require filtered, resettable or nonresettable power. The FCPS-24FS6
can provide up to 4 amps of continuous current and the FCPS-24FS8 can provide up to
6 amps of continuous current. The power supply must be set for Split Alarm mode.
Output circuits 1 & 2 are configured as resettable power outputs by connecting the
resettable power from an FACP to Control Input 1 Terminals 3(+) & 4(-) on TB4 of the
FCPS-24FS. Output circuits 3 & 4 are configured as nonresettable power outputs by
connecting jumpers between the auxiliary 24 VDC output on TB4 to the Control Input
2 terminals on TB4 [Terminals 9(+) to 7(+) and 1(-) to 8(-)].
Note: All four outputs can be configured as resettable or all four can be configured as
nonresettable by setting the power supply for General Alarm and then connecting a
resettable power source to Control Input 1 or a nonresettable power source, such as the
Aux. Power output of the FCPS-24FS, to Control Input 1.
For addressable panel applications, an addressable monitor module can be used to
monitor the trouble contact of the FCPS-24FS and the resettable power connection
from the FACP using an End-of-Line power supervision relay. If the FCPS-24FS enters
a trouble condition, the Normally Closed trouble contact will open and if the resettable
power from the FACP is lost, the Normally Closed power supervision relay contact will
open.
TB
4
JP
3
J3
TB5
TB2
JP
1
JP
2
OU
T
4
-NAC4
+
OU
T
3
-NAC
3
+
OU
T
2
-N
AC2
+
OU
T
1
-NAC1
+
AU
X
-
IN
2
-
IN
2
+
OU
T
1
-
OU
T
1+
IN
1-
IN
1+
SY
N
C
IN
-
S
Y
N
C
IN
+
AU
X
+
NO
NC
AUX
T
B
L
CO
M
1 2 3 4 5 6 7 8 9 10
8
7
6
5
4
3
2
1
3
2
1
8
9
8
8
9
9
10
11
12
13
14
15
0
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
0
1
2
3
4
7
6
5
TENS
ONE S
ADDRES S
LOO P
Figure 5.4 Remote Power Supply Application
Power Output 1
Resettable
Power Output 2
Resettable
Power Output 3
Nonresettable
Power Output 4
Nonresettable
SLC
SLC
Monitor Module
FACP
24 VDC
Resettable
Power
FCPS-24FS
EOL Power
Supervision Relay
A77-716B
(energized)
SW1 Switch Settings
1 = OFF
2 = OFF
3 = OFF (master)
4 = OFF (no AC Fail reporting delay)
5 = OFF
6 = ON
7 = OFF (charger enabled)
8 = OFF (circuit 4 NAC)
Split Alarm
No Sync
End-of-Line Resistor supplied
with Monitor Module
24f