background image

Features

1. Introduction

LDM-32F  PN 50055:C  03/20/01

11

LDM-E32F

Each LDM-E32F expander module provides 32 additional lamp/LED driver 
outputs from J5, J6, J7 and J8.  The expander module has a slide switch SW4 
for selecting alarm or alarm and trouble annunciation and an input for a local 
lamp test switch.  In alarm mode, use only one LDM-32F and one LDM-E32F 
for a maximum of 56 alarm indicators and 8 system status indicators.  In alarm/
trouble mode, use one LDM-32F and three LDM-E32Fs for a maximum of 56 
alarm indicators, 56 trouble indicators, 16 status indicators and 64 optional 
control switch inputs.  Multiple sets of LDM-32Fs with LDM-E32F expanders 
increase the system annunciation capabilities beyond 56 zones or points.  This 
is possible by various settings of address switches SW1 and SW2 on the LDM-
32F (refer to Appendices).  Each LDM-E32F is supplied with a 26-conductor 
expander ribbon cable, 4 standoffs and 4 screws.  

Figure 2  LDM-E32F

LD

M-

E

3

2F.cd

r

Output Connectors 
for Wiring to LEDs

Ribbon Cable 
Connections to 
Next LDM-E32F

Ribbon Cable 
Connections from 
LDM-32F or 
Previous LDM-E32F

Security Key

Switch Terminal

Control Switch

Terminal

Alarm or

Alarm/Trouble

Slide Switch

Not Used

Summary of Contents for LDM-32F

Page 1: ...Lamp Driver Module LDM 32F Instruction Manual Document 50055 03 20 2001 Rev C PN 50055 C0 ECN 01 155...

Page 2: ...xplosions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined...

Page 3: ...pated or encountered Disconnect AC power and batteries prior to removing or inserting circuit boards Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling filing...

Page 4: ...4 LDM 32F PN 50055 C 03 20 01 This page intentionally left blank...

Page 5: ...witch 13 SW4 Alarm Trouble Mode Switch 13 Terminal Blocks 14 TB1 24 VDC Power Earth Ground and Supervision 14 TB2 EIA 485 In Out 14 Cables 14 Expander Ribbon Cable 14 The LDM CBL24 and LDM CBL48 14 Ke...

Page 6: ...nd Testing the LDM 32F 33 Power Supply Connection 34 MPS 24AF Main Power Supply 34 MPS 24BF Main Power Supply 34 EIA 485 Connection 34 Lamp LED Driver Operation 35 Alarm Only Operation 37 Alarm Only O...

Page 7: ...tion Diagram 49 Appendix C MS 9600 Capabilities 51 Trouble Indication 51 Programming and Testing the LDM 32F 51 Power and EIA 485 Connections 51 Configuration 52 Setting Rotary Switches 52 Alarm Only...

Page 8: ...8 LDM 32F PN 50055 C 03 20 01 This page intentionally left blank...

Page 9: ...of NAC outputs Alarm relay activation Other control functions The modules interface to the host fire alarm control panel via an EIA 485 communications bus circuit A maximum of 32 LDM 32Fs may be conn...

Page 10: ...d troubles and other functions Switch SW4 is used to configure the module to annunciate 32 alarms or 16 troubles A green ON LINE LED flashes to indicate ongoing communications withthehostFACP OneLDM 3...

Page 11: ...um of 56 alarm indicators 56 trouble indicators 16 status indicators and 64 optional controlswitch inputs Multiple sets ofLDM 32Fswith LDM E32F expanders increase the system annunciation capabilities...

Page 12: ...ctor is provided as an input on LDM 32F and LDM E32F modules for an external security key switch Key switch contacts must be Normally Closed The keyswitchpreventsunauthorizeduse ofremote control switc...

Page 13: ...system requiring annunciation of alarms and troubles for all 198 points would require four sets of LDMs with addresses 01 02 03 and 04 The MS 9600 is an exception refer to Appendix C MS 9600 on page 5...

Page 14: ...IA 485communicationsbuscircuitforproperoperation The EIA 485 bus carries commands and data sent between the host FACP and the LDMs The input must be power limited Cables Expander Ribbon Cable The Expa...

Page 15: ...ity A UL listed key lock switch wired to J4 on the LDM 32F should be used to provide access security for all control switches wired to that set of LDM modules Note Control switches will not function w...

Page 16: ...1 Introduction Related Documentation 16 LDM 32F PN 50055 C 03 20 01 NOTES...

Page 17: ...provided by custom graphic annunciator manufacturers may be used provided they meet UL requirements as UL listed secured enclosures CHS 4L Chassis The CHS 4L chassis will support one LDM 32F module a...

Page 18: ...tional modules or expanders Figure 5 Installing LDM Modules in CHS 4L Connect an expander ribbon cable P N 75120 from the LDM 32F connector J2 to J3 of the first LDM E32F expander module If multiple L...

Page 19: ...wire resistance to 10 ohms Connect the Grounding Cable from the chassis to the earth ground terminal of TB1 EARTH Connect 24 VDC power to the POWER IN and COMMON IN terminals of TB1 Figure 7 24 VDC Po...

Page 20: ...dules used Communications between the Fire Alarm Control Panel and the LDM 32F is accomplishedoveratwo wireEIA 485serialcommunicationsbuswhichmust be power limited Communications between the host FACP...

Page 21: ...ld in Conduit EIA 485 Shield Not in Conduit When the EIA 485 wiring is not in conduit terminate the shield at the outside of the FACP cabinet Do not allow the shield to enter or even touch the cabinet...

Page 22: ...he EIA 485 Out terminals at the last LDM 32F on the circuit see below All other LDM 32Fs should not have a resistor installed Figure 12 EIA 485 Terminal Block TB2 Multiple wiring of EIA 485 circuits F...

Page 23: ...lt output from LDM 32F J11 pin 1 Figure 14 Typical LDM to Graphics Display Connection 5VDC The figure below illustrates LEDs being powered by the 24 volt output from LDM 32F J9 pin 3 Figure 15 Typical...

Page 24: ...must be key lock type secured in a locked enclosure or a security key switch must be installed to control access All switches must be installed in the same room as and no more than 20 feet from the L...

Page 25: ...e arrow on SW2 tens so it points to 0 and position the arrow on SW1 ones so it points to 1 Figure 17 Address Switches SW1 SW2 Function DIP Switch SW3 These switches are used to determine how the LDM 3...

Page 26: ...LDM series hold the same address all but one must be configured as Receive Only 6 Piezo Disable Set this switch ON to disable the piezo from sounding for any event The piezo will also be disabled if F...

Page 27: ...t control panel Graphic Annunciator Lamps LEDs To adhere to standard fire alarm control panel convention and remain consistent with otherproducts that may exist in the system the following color conve...

Page 28: ...3 Operation Graphic Annunciator Lamps LEDs 28 LDM 32F PN 50055 C 03 20 01 NOTES...

Page 29: ...nd of the EIA 485 bus it willprovidesupervision ofReceiveOnly LDMs located on theEIA 485 bus between the Receive Transmit LDM and the FACP Receive Transmit LDM 32F LDMs that are configured to serve as...

Page 30: ...4 LDM Communications Receive Transmit LDM 32F 30 LDM 32F PN 50055 C 03 20 01 NOTES...

Page 31: ...larm and Trouble Display Mode and employing three expanders could have as many as 128 LEDs all of which are activated during Lamp Test Maximum Current per Driver 100 mA external circuit must limit cur...

Page 32: ...n tables of the installation manual 2 EnterAlarmCurrentTotalobtainedhereintothealarmcalculationtables of the installation manual Table 3 Power Requirement Calculations Standby Current Number of LDM 32...

Page 33: ...can 2000 Manual System Control Switches Acknowledge Signal Silence System Reset Activate selected system outputs notification circuits relays System Control Switches on the Sensiscan 2000 CPU may be r...

Page 34: ...ore than 200 mA current can be drawn from these terminals in standby or alarm Figure 22 MPS 24BF Power Supply Connections EIA 485 Connection The EIA 485 bus that communicates with the LDM must be conn...

Page 35: ...as shown above to points 57 through 64 provided those points exist in the system and the LDM 32F is set to address 01 Alarm Red LED Trouble Supv Yellow LED Control Switches2 2 Optional control switch...

Page 36: ...Status per Circuit Trouble Status per Circuit Not Used IZ 4F IZE 4F Alarm Status per Circuit Trouble Status per Circuit Not Used IC 4F IC 4CCF Indicates Activation2 2 These Status LEDs are active only...

Page 37: ...nts P57 through P64 dedicated to the Sensiscan 2000 system status annunciation see Figure 24 below Itisassumedthatthe 8 PointShift willbeselectedonlyonsystemscontaining 56 zones points or less or a to...

Page 38: ...configuration of the LDM Series modules to annunciate alarms and troubles for up to 56 zones points with the last eight points 16 LEDs J7 P1 through P8 and J8 P1 through P8 dedicated to Sensiscan 2000...

Page 39: ...4 Zones or Points Alarm Second 4 Zones or Points Trouble Second 4 Zones or Points Alarm Third 4 Zones or Points Trouble Third 4 Zones or Points Alarm Fourth 4 Zones or Points Trouble Fourth 4 Zones or...

Page 40: ...32F and are assigned to Circuits 57 through 64 as shown below Note It is assumed that Sensiscan 2000 systems with 8 Point Shift selected will be 56 zones points or less Table 10 Switch Control Functio...

Page 41: ...the panel s display Programming and Testing the LDM 32F After complete installation the Lamp Driver Module s must be programmed into the control panel as if it were an annunciator After programming t...

Page 42: ...f address 01 dedicated to the MS 9200 system function LEDs see Figure 29 below Table 11 Alarm Only Setup Alarm Only Annunciation of Zones With 8 Point Shift The table below illustrates the configurati...

Page 43: ...es to annunciate the alarm and trouble states for all 56 softwarezoneswiththelasteightpointsofaddress 01 dedicatedtotheMS 9200 system functions as listed below see Figure 32 on page 44 Table 14 Alarm...

Page 44: ...18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 J5 J6 J7 J8 LCM32F conn cdr Alarm First 4 Zones or Points Trouble First 4 Zones or Points Alarm Second 4 Zones or Points Trouble Second 4 Zones or Points...

Page 45: ...address 03 and 04 for modules Table 16 Alarm Only Setup Modules LDM Module Address 01 LDM Output Connectors J5 J6 J7 J8 LDM 32F Sys Funct 1 to 8 9 to 16 17 to 24 LDM E32F 25 to 32 33 to 40 41 to 48 4...

Page 46: ...dules Set address 03 and 04 for modules Table 18 Alarm Only Setup Modules shift LDM Module Address 01 LDM Output Connectors J5 J6 J7 J8 LDM 32F 1 to 8 9 to 16 17 to 24 25 to 32 LDM E32F 33 to 40 41 to...

Page 47: ...32F System Functions 1 to 4 5 to 8 1st LDM E32F 9 to 12 13 to 16 17 to 20 21 to 24 2nd LDM E32F 25 to 28 29 to 32 33 to 36 37 to 40 3rd LDM E32F 41 to 44 45 to 48 49 to 52 53 to 56 LDM Module Address...

Page 48: ...5 J6 J7 J8 LDM 32F 1 to 4 5 to 8 9 to 12 13 to 16 1st LDM E32F 17 to 20 21 to 24 25 to 28 29 to 32 2nd LDM E32F 33 to 36 37 to 40 41 to 44 45 to 48 3rd LDM E32F 49 to 52 53 to 56 System Functions LDM...

Page 49: ...2F addressed as 01 must be placed at the end of the EIA 485 circuit in order to provide electrical supervision of the wiring between all LDMs on the loop Figure 33 Configuration for 198 Point Alarm Tr...

Page 50: ...Appendix B MS 9200 Configuration 50 LDM 32F PN 50055 C 03 20 01 NOTES...

Page 51: ...EIA 485 bus is supervised by the MS 9600 Loss ofcommunication results in system trouble message on the panel s display Programming and Testing the LDM 32F After complete installation the Lamp Driver M...

Page 52: ...s 1 56 2 0 2 Zones 57 99 2 NACs 3 0 3 Loop 1 Address M1 M64 4 0 4 Loop 2 Address M1 M64 5 0 5 Loop 1 Address M65 M128 6 0 6 Loop 2 Address M65 M128 7 0 7 Loop 1 Address M129 M159 Loop 2 Address M129 M...

Page 53: ...9600 system functions see Figure 35 below Table 25 Alarm Only Setup with Shift Figure 35 System Functions to Output Connectors 1 LDM Module Address 01 LDM Output Connectors J5 J6 J7 J8 LDM 32F Sys Fu...

Page 54: ...Setup with Shift LDM Module Address 01 LDM Output Connectors J5 J6 J7 J8 LDM 32F System Functions Z1 to Z4 Z5 to Z8 1st LDM E32F Z9 to Z12 Z13 to Z16 Z17 to Z20 Z21 to Z24 2nd LDM E32F Z25 to Z28 Z29...

Page 55: ...conn cdr Alarm First 4 Zones or Points Trouble First 4 Zones or Points Alarm Second 4 Zones or Points Trouble Second 4 Zones or Points Alarm Third 4 Zones or Points Trouble Third 4 Zones or Points Al...

Page 56: ...rol panel s SLC Loop 1 Modules M65 to M128 in Alarm Trouble mode See Figure 36 on page 55 By referring to Table 23 on page 52 it can be determined what address can be set to annunciate any other group...

Page 57: ...39 44 55 56 alarms 10 37 alarms and troubles 38 annunciation capabilities 11 annunciator functions 13 annunciators 29 B battery 9 BCD switches 13 bipolar 12 31 C CAB A3F and CAB B3F 17 cabinet 21 cabi...

Page 58: ...s 20 group of address points 56 I I O module 40 I O point 33 41 51 impedance 20 indicating device circuit 27 initiating circuits 33 initiating device circuit 27 intermediate display 29 J J1 32 J2 14 1...

Page 59: ...32 programmed 33 41 42 51 R Receive Only 13 26 Receive Transmit 13 49 red 23 regulated 14 relay circuits 27 remote control switches 9 12 remote location 29 remote switch functions 10 removable termin...

Page 60: ...51 time control circuits 27 track 35 transient protection 17 trouble 11 trouble condition 27 trouble drivers 24 trouble indication 12 trouble indicators 11 trouble points 23 trouble signal 14 20 trou...

Page 61: ...LDM 32F PN 50055 C 03 20 01 61...

Page 62: ...62 LDM 32F PN 50055 C 03 20 01...

Page 63: ...ansportation prepaid to the manufacturer This writing constitutes the only warranty made by this manufacturer with respect to its products The manufacturer does not represent that its products will pr...

Page 64: ...World Headquarters One Fire Lite Place Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www firelite com...

Reviews: