LDM-32F PN 50055:C 03/20/01
41
Appendix B: MS-9200
Capabilities
When installed with a MS-9200, the LDM Series modules can annunciate the
status of 56 software zones or 198 points plus system status. Each lamp driver
output is assigned to one and only one system I/O point:
Addressable Devices -
Detectors -
SD350, SD350T, CP350, H350, H350R, D350P & D350LP
Monitor Modules -
MMF-300, MMF-301, MMF-302 & MDF-300
Control Modules -
CMF-300
Addressable Pull Stations -
BG-12LX
System Control Switches -
Acknowledge, Signal Silence, System Reset & Drill
Trouble Indication
Communication between the MS-9200 and the LDMs is accomplished over a
two-wire EIA-485 serial communication bus. The EIA-485 bus is supervised
by the MS-9200. Loss of communication results in system trouble message on
the panel’s display.
Programming and Testing the LDM-32F
After complete installation, the Lamp Driver Module(s) must be programmed
into the control panel as if it were an annunciator. After programming the fire
alarm control panel to accept them, fully test the LDM(s) by ensuring that each
switch and LED performs its intended function, and that the LDM(s) can
perform the functions outlined in "3. Operation" on page 27.
Power and EIA-485 Connections
Regulated 24 VDC power and the EIA-485 communication circuit must be
connected to the MS-9200 as illustrated below.
Note:
An external power source may be used to power the LDM Series.
Figure 28 MS-9200 Circuit Board connections
24V UNREG 24V NON RS 24V RST
BE LL 2 P OWER
BE LL 1 P OWER
SUPV
ALARM
TROUBLE
B+ A + A- B-
B+ A + A- B-
NO C NO NC C NO NC C
A B B+ A+ B- A -
1 COMM 2
ACS
SHIELD
SLC
SLC
OUT+ IN+ O UT- IN-
T
B
4
T
B
2
T
B
1
T
B
3
T
B
7
T
B
5
T
B
6
L
D
M32F
-92
00.cdr
To LDM TB1 -
Power IN (+)
Power IN (–)
To LDM TB2 -
EIA-485 IN (+)
EIA-485 IN (–)
Summary of Contents for LDM-32F
Page 4: ...4 LDM 32F PN 50055 C 03 20 01 This page intentionally left blank...
Page 8: ...8 LDM 32F PN 50055 C 03 20 01 This page intentionally left blank...
Page 16: ...1 Introduction Related Documentation 16 LDM 32F PN 50055 C 03 20 01 NOTES...
Page 28: ...3 Operation Graphic Annunciator Lamps LEDs 28 LDM 32F PN 50055 C 03 20 01 NOTES...
Page 30: ...4 LDM Communications Receive Transmit LDM 32F 30 LDM 32F PN 50055 C 03 20 01 NOTES...
Page 50: ...Appendix B MS 9200 Configuration 50 LDM 32F PN 50055 C 03 20 01 NOTES...
Page 61: ...LDM 32F PN 50055 C 03 20 01 61...
Page 62: ...62 LDM 32F PN 50055 C 03 20 01...