S2000 15017 Rev H 10/08/96 P/N 15017:H
22
4.2
UL P
OWER
-
LIMITED
W
IRING
R
EQUIREMENTS
- P
OWER
S
UPPLIES
The diagram below shows a typical Sensiscan 2000 installation and is provided as a guide for proper wiring placement. The
AC and battery wiring are not power-limited. A separation of at least 0.25" must be maintained between power-limited and
nonpower-limited wiring. Install the tie wraps and adhesive squares as indicated below.
Figure 4-2: Power-limited and Nonpower-limited Wiring for Power Supplies
Adhesive square and
tie-wrap on back of
cabinet and on top of
power supply chassis
affixing nonpower-
limited wiring.
Adhesive square and tie-
wrap on back of cabinet
affixing power-limited
wiring.