S2000 15017 Rev H 10/08/96 P/N 15017:H
23
Figure 4-3: Field Wiring the CPU
UL-listed
24 VDC
Polarized Horn
UL-listed
24 VDC
Polarized Bell
Municipal box wiring
must be run in conduit.
Remote Station
Trouble Output
Remote Station
Alarm Output
24 VDC (nominal). 10 mA max rated
current. Internal resistance = 1360 ohms
(nominal).
Intended for connection to the polarity
reversal circuit of a remote station receiv-
ing unit (Fire-Lite Model RS-82) having
compatible ratings.
Non-Supervised
Remote Station Outputs
Non-Supervised, Power-limited
(Standby polarity shown)
Trip current = 0.25 Amps (min)
Coil voltage = 3.65 VDC (min)
Coil resistance = 14.6 ohms (max)
Style Z
4.7K, 1/2 watt ELR,
Part # 71252.
Style Y
Typical Supervised Power-limited
Notification Appliance Circuits
Use only compatible, UL-listed notification ap-
pliances (see the Device Compatibility Docu-
ment, 15378). Max current per circuit is 3.0
amps, subject to the limitations of the power
supply.
Municipal Box Ratings
Nonpower-limited, supervised for
open circuits. Max. Current (short
circuit) = 0.6 amps. Max. Voltage
(open circuit) = 27.6 VDC. Max.
Wire Resistance = 5 ohms.
Municipal Box Output
Nonpower-limited and super-
vised (for open circuits). Wir-
ing can leave the building.
Municipal Box Output
1)
The Remote Station Alarm Output and the Municipal Box Output must not be used simultaneously.
2)
Notification appliance circuits, Remote Station Trouble output, and the Remote Station Alarm output are power-
limited and may be connected to limited-energy cable.
3)
Wire notification appliances according to the manufacturer's instructions packaged with each device.
4)
Terminal blocks will accept #12 to #22 AWG wire.
5)
Size notification circuit wire for a maximum drop of 2 volts DC at the last device on the circuit.
6)
The RS-1459 module is required when the Remote Station or Municipal Box Output is connected to a circuit that
exits the protected premises.
Exception
- The RS-1459 module is not required for the Municipal Box Circuit if
ALL of the following conditions exist: (1) wiring is in conduit, (2) wire length is less than 1000 meters, and (3)
wiring does not cross any power lines.
Programmable
Alarm
Contacts
(power-limited
source only)
5A @ 30VDC
5A @ 120VAC
(resistive)
System
Trouble
Contacts
(power-limited
source only)
2A @ 30VDC
1A @ 120VAC
(resistive)