S2000 15017 Rev H 10/08/96 P/N 15017:H
25
b+ b- b+ b- b+ b- b+ b- b+ b- b+ b- b+ b- b+ b-
A B
C D
E* F* G* H*
A
E
B
F
C
G
D
H
Manual Pull Station
UL-listed two-wire
Photo smoke detector
2
UL-listed two-wire
Ion smoke detector
2
4.7K, 1/2 watt ELR, Part # 71252.
5
1)
Initiating device circuits are supervised, power limited and may be con-
nected to limited-energy cable, except for initiating devices that require
24 VDC power.
2)
Use only the compatible, UL-listed two-wire smoke detectors that are
listed in FireLite Document 15384.
3)
For connection of four-wire smoke detectors, refer to Section Six.
4)
Wire initiating devices according to the manufacturer's instructions pack-
aged with each device.
5)
For Canada, model F-ELR End-of-Line Resistor Assembly required.
6)
Maximum line resistance is 100 ohms.
Typical NFPA Style B
Initiating Device Circuit
Supervised and Power-limited
Dummy load all unused circuits
with 4.7K ELR (71245).
*NOTE: IZ-4F contains only circuits A, B, C and D.
F
IGURE
4-5 NFPA S
TYLE
B F
IELD
W
IRING
OF
I
NITIATING
Z
ONE
M
ODULES