S2000 15017 Rev H 10/08/96 P/N 15017:H
32
CPU
(bottom view)
Bottom
view
of ICM-4F
or ICE-4F
If powering a notification circuit module from the
main power supply, connect the Auxiliary Bell Power
Harness (71091) from J6 on the CPU to J5 on the ICM-
4F or ICE-4F. See Section 6.9 for more information.
Connector orientation
7-position end
Note position of Red
Wire at 8-position end
Power Ribbon
(71085)
Main Pwer
Supply Bell
Power
Harness (71093)
Blue wire
Power Harness
(71086)
Connect to P2 or P4.
(ICM-4F)
(ICE-4F)
F
IGURE
5-2 H
ARNESS
C
ONNECTIONS
FOR
THE
MPS-24A
+ -
MPS-24AF/
MPS-24AFE