S2000 15017 Rev H 10/08/96 P/N 15017:H
43
Figure 6-3: Transmitter Connections
1)
Connection between Sensiscan 2000 and the transmitter is supervised by the transmitter.
2)
Use transformer mode ULT STK NO. 100391 (listed, Class 2, 12 V, 10VA.). See Potter Electric Signal
Company Bulletin #748.
3)
This Sensiscan 2000/Transmitter arrangement can be employed for an NFPA 72-1993 Central Station Fire Alarm
System, NFPA 72-1993 Remote Station Fire Alarm System, or NFPA 72-1993 Proprietary Fire Alarm System.
Form-C Trouble contact which will
automatically activate on any Trouble
condition.
CPU-2000
Form C Alarm contact programmed
to activate on General Alarm.
Sensiscan 2000
6.7
P
ROPRIETARY
P
ROTECTIVE
S
IGNALING
The Sensiscan 2000 can be employed as a Proprietary Protective Premises Control Unit when used in conjunction with a
compatible, UL-listed receiving unit.