S2000 15017 Rev H 10/08/96 P/N 15017:H
6
1.4
M
INIMUM
S
YSTEM
C
ONFIGURATIONS
At a minimum, the following Sensiscan components are required for compliance with NFPA standards 12, 12A, 12B and 72-
1993.
BE-2000 Basic Equipment Package
which includes:
CPU-2000 Central Processor Module, Vented Dress Panel, CHS-4F Chassis, and connecting
cables.
An IZ-4F or IZ-8F Initiating Zone Module
for up to eight Style B initiating device circuits.
The
Main Power Supply
(MPS-24AF/MPS-24AFE or MPS-24BF/MPS-24BFE)
Standby Batteries
- refer to Standby Power Requirements, Appendix A.
A
Sensiscan 2000 Cabinet
(CAB-A3F or CAB-B3F)
In addition, the following equipment is required for the specific NFPA standards listed below.
An NFPA 72-1993 Proprietary Protected Premises Control Unit requires:
Potter Electronic Signal Co. Transmitter
(Model EFT-C) with transformer (Model ULT, Stock. Number 1000391).
An NFPA 72-1993 Central Station Protected Premises Control Unit requires:
UDACT-F, 911A Digital Communicator or an Ademco No. 678 UL-F Digital Communicator
Sprinkler Supervisory and/or Waterflow Alarm Service requires a
Control Relay Module.
An NFPA-12 Minimum Carbon Dioxide Extinguishing Control Unit, NFPA-12A Halon 1301 Fire Extinguishing Control
Unit, NFPA-12B Halon 1211 Fire Extinguishing Control Unit requires:
TC-2F or TC-4F Time Control Module.
NOTE
For wiring diagrams and more information on these applications, refer to Section 6.