Appendix
9.6.1.6 M
AIN
T
ERMINATION
B
OARD
–
C
ONNECTING
R
ELAY
O
UTPUTS
4 x Clean Contact Relays
NO
CM
NC
TERM 1
NO
CM
NC
NO
CM
NC
NO
CM
NC
-COM A
+COM A
-COM B
+COM B
TERM 5
+POW A
-POW A
+POW B
-POW B
+AZ1
-AZ1
+AZ2
-AZ2
TERMINATION BOARD
9.6.1.7 M
AIN
T
ERMINATION
B
OARD
–
P
ANEL
E
XPANSION
R
ELAYS
J16
J17
OUT
IN
Note that the panel expansion relay boards must be connected in a closed serial loop between
J16 and J14 on the Main Termination Board for the software to auto-detect the actual number of
Relay boards connected. The maximum allowed is 8 x 8 way relay boards. If the serial loop is left
open, the panel will assume that all 8 boards are present.
Note: If no expansion relay boards are used, jumper pins J18, situated close to the J14 connector,
must be shorted together.
AFP-2800/2802 Manual
– P/N DOC-01-011
114
4 x Monitored 24V Outputs (4k7 EOL Resistors)
+
BELL
-
+
W/SYS
-
+
PR3
-
+
PR4
-
NO
CM
NC
NO
CM
NC
NO
CM
NC
NO
CM
NC
TERM 5
Comms
Terminal
TERM 2
TERM 4
TERMINATION BOARD
Summary of Contents for AFP-2800