Specifications & Approvals
4.3
E
LECTRICAL
S
PECIFICATIONS
Note: All functions and specifications described in this Operators Manual are subject to change without notice.
4
4
.
.
3
3
.
.
1
1
P
P
O
O
W
W
E
E
R
R
S
S
U
U
P
P
P
P
L
L
Y
Y
Parameter
PS243
PS249
NPS-2
NPS-5
NPS-11
(3Amp)
(9Amp)
(2.6amp)
(5.5amp)
(11.7amp)
Input Voltage
240V AC +/-
240V AC +/-
110 or 240
Universal
Universal
10%
10%
(SW select)
Input Range
216V AC to
216 V AC to
85-132/170-
85-264VAC
88-264VAC
254V AC
254V AC
264VAC
Auto Ranging
Auto Ranging
(SW select)
Output Voltage
24V DC nom.
24V DC nom.
24V DC nom.
24V DC nom.
24V DC nom.
27.6V DC no
27.6V DC no
27.3V DC no
27.3V DC no
27.3V DC no
load
load
load
load
load
26.5 V DC full
26.5V DC full
27.3V DC full
27.3V DC full
27.3V DC full
load
load
load
load
load
Adjustable
12V DC to 30V
12V DC to 30V
+/-10%
+/-10%
26V to 32V
Range
DC
DC
Rated Current
3.0A @ 26.5V
9.0A @ 26.5V
2.6A @ 27V DC
5.5A @ 27V DC
11.7 @ 27V DC
Of Power Supply
DC
DC
Overload
7.4A @ Short
20A @ Short
105% to 150%
105% to 150%
105% to 135%
Current Device
Circuit
Circuit
of rated power
–
of rated power
–
of rated power
–
auto recovery
auto recovery
auto recovery
after fault
after fault
after fault
removal
removal
removal
Secondary
5A
15A
N/A
N/A
N/A
Transformer
Fuse
Max Ripple
150mV p-p
150mV p-p
120mV p-p
150mV p-p
200mV p-p
Load Regulation
2%
2%
± 0.5%
± 0.5%
± 0.5%
Line Regulation
2%
2%
± 0.5%
± 0.5%
± 0.2%
Efficiency
>80%
>80%
82%
84%
88%
Battery Test
Internal: 15
Internal: 15
External Load
External Load
External Load
ohms
ohms
Battery Test
10A
15A
N/A
N/A
N/A
Relay Contact
Rating
Indicators
Mains On,
Mains On,
Mains On,
Mains On,
Mains On,
Output On
Output On
Charger Fault,
Charger Fault,
Charger Fault,
Battery Fault,
Battery Fault,
Battery Fault,
Battery test,
Battery test,
Battery test,
Batt test inhibit
Batt test inhibit
Batt test inhibit
Status Indicators
By External
By External
Onboard LED or
Onboard LED or
Onboard LED or
Interface or FIP
Interface or FIP
External
External
External
Interface or FIP
Interface or FIP
Interface or FIP
Environmental
-10
°
C to +55
°
C
-10
°
C to +55
°
C
-10
°
C to +55
°
C
-10
°
C to +55
°
C
-10
°
C to +55
°
C
Dry heat
Dry heat
Dry heat
Dry heat
Dry heat
+ 40
°
C @ 93%
+ 40
°
C @ 93%
+ 40
°
C @ 93%
+ 40
°
C @ 93%
+ 40
°
C @ 93%
RH
RH
RH
RH
RH
WARNING: Severe damage may occur if the batteries are connected incorrectly.
Note:
When annunciators or field modules are powered from external power supplies, use a separate conductor to
connect the main power supply common terminal (-0V) to the remote power supplies common terminal (-0V).
AFP-2800/2802 Manual
– P/N DOC-01-011
12
Summary of Contents for AFP-2800
Page 139: ...Appendix 9 12 PANEL EXPANSION RELAYS AFP 2800 2802 Manual P N DOC 01 011 139...