Appendix
9.6.5.2 N
OTI
.F
IRE
.N
ET
™
NCM
S
WITCHES
&
T
ERMINATIONS
Network connection
ports (NUP)
Channel A & B
connections
Ground Fault
detection switches
and Network End Of
Line Termination
Resistor switches
From last node,
Port A
B
A
Note:
Wiring from the NCM-W that is installed outside buildings:
- Must be in conduit and be buried in a trench separate from any power lines
NCM-W Connections:
Connector Pin
Signal Name
TB100-1
CH-A (+)
TB100-2
CH-A (-)
TB100-3
CH-B (+)
TB100-4
CH-B (-)
TB100-5
Earth Ground
AFP-2800/2802 Manual
– P/N DOC-01-011
- Cannot cross any power lines
Not used
Diagnostic LEDs
To next node,
Port B
B
A
CONNECTION
DETAIL
Channel-A Driver / Receiver
Channel-A Driver / Receiver
Channel-B Driver / Receiver
Channel-B Driver / Receiver
123
Summary of Contents for AFP-2800