Both Operating Mode switches (SW4 & SW5) on the PCB must be set for ACS Mode (the UP position).
Event sounder:
Setting DIP Switch 1 of SW1 to OFF will disable the buzzer for alarms. Setting DIP Switch 2 of SW1 to OFF will
disable the buzzer for faults. IF THE BUZZER IS ENABLED, PR
ESSING THE “MUTE” BUTTON WILL SILENCE THE BUZZER UNTIL A
new event is received.
Addressing Terminal Mode:
SW2 & SW3 set the address as per the table below. NOTE THAT
“200” IS ADDED TO THE ACTUAL VALUES OF SW2 & SW3
to give an address in the range 201
– 239. Setting all switches to off will take the LCD-80 offline.
Addressing Annunciator Mode:
SW2 & SW3 SET THE ADDRESS AS PER THE TABLE BELOW. NOTE THAT
“100” IS ADDED TO THE ACTUAL VALUES OF SW2 & SW3
to give an address in the range 101
– 139. Setting all switches to off will take the LCD-80 offline.
AFP-2800/2802 Manual
– P/N DOC-01-011
138
SW3-1
SW3-2
SW2
Actual Address
OFF
OFF
1
– 9
101
– 109
ON
OFF
0
– 9
110
– 119
OFF
ON
0
– 9
120
– 129
ON
ON
0
– 9
130
– 139
SW3-1
SW3-2
SW2
Actual Address
OFF
OFF
1
– 9
201
– 209
ON
OFF
0
– 9
210
– 219
OFF
ON
0
– 9
220
– 229
ON
ON
0
– 9
230
– 239
Next
Previous
Mute
SW4
SW5
10 SEPT 12:34
1/1
EAST WING
1.2.Z6
FAULT
A=0
F=1
I=0
RS485 Comms
connector
24V Power
connector
Appendix
9
9
.
.
1
1
1
1
.
.
7
7
Note:
Summary of Contents for AFP-2800
Page 139: ...Appendix 9 12 PANEL EXPANSION RELAYS AFP 2800 2802 Manual P N DOC 01 011 139...
Page 156: ...Notes...
Page 157: ......
Page 158: ......