Panel Operation
7.3.3.7.1.1 Service Menu
– List – List – Analog – Detectors – Status
This screen will show a reading of the selected Analog addressable detector updated every 3 seconds, 255 times.
THE DETECTOR’S CURRENT CONFIGURATION IS DISPLAYED TOGETHER WITH “LIVE READINGS” AS SHOWN BELOW.
Heat Detector
Smoke Detector
DAY MODE
20 JULY 2002 14:44:37
L1D3
(Z990) > APARTMENT 1 BEDROOM
Poll Mode
> FlashScan Mode
Programmed As
> PHOTO-OPTICAL
Actual Device
> PHOTO-OPTICAL
Device State
> NORMAL
Device Status
> NORMAL
LED Status
> Polling
Detector Values: (Needs Cleaning)
Alarm
= 0%
Peak Alarm Value
= 10%
Prealarm
= 0%
Day Alm Sensitivity = 5
Compensation = 81% Day PreAlarm Sens
= 5
Night Alarm Sens
= 1
Night PreAlarm Sens = 1
Device Scanned 255 Times
.
NEXT
TEST
RESET
Menu
Note:
“ZXXX” IS DISPLAYED AFTER THE DESCRIPTOR, XXX IS THE ZONE NUMBER MAPPED TO THE DETECTOR. A ZONE NUMBER OF 0
is an indication that the detector is not mapped to a zone.
Actions:
•
Press the
PREV
buttons to move to the previous installed point.
•
Press the
NEXT
buttons to move to the next installed point.
•
Press the
TEST
button to enter test menu for the detector.
•
Press the
RESET
button to re-initialise the detector.
•
Press
MENU
to return to the Analog Menu screen.
Explanations of terms:
Description
Shows the current polling protocol being used. FlashScan = 10
detectors at a time, CLIP = 1 detector at a time. Polling mode is
auto sensed at start-up
Detector type programmed into panel
Detector type physically seen on loop
Shows alarm or activated condition of point
DETAILED DESCRIPTION OF FAULT CONDITION.
I.E.: “NO RESPONSE”
Polling, On, Off, Polling ID
Current Percentage of alarm or Degree Celsius
Current Percentage of Pre-alarm
Highest reading since last reset
Please refer to page
Error! Bookmark not defined.
for
information on Drift Compensation
Detector sensitivity for day/night, alarm/pre-alarm. Please refer to
page 105 for explanation information on sensitivity settings
36
20 JULY 2002 14:44:37
L1D2
(Z001) > APARTMENT 1 BATHROOM
Poll Mode
> FlashScan Mode
Programmed As
> HEAT
Actual Device
> HEAT
Device State
> NORMAL
Device Status
> NORMAL
LED Status
> Polling
Detector Values:
Alarm
= 0%
Peak Temperature
= 30 C
Temperature = 24 C
Day Alm Sensitivity= 5
Night Alarm Sens
= 1
DAY MODE
PREV
PREV
Device Scanned 255 Times
.
NEXT
TEST
RESET
Menu
ANALOG MENU – STATUS
A = 0
F = 0
I = 0
N = 0
ANALOG MENU – STATUS
A = 0
F = 0
I = 0
N = 0
Range
FlashScan or CLIP
9 Types
9 Types
Normal/Active/Alarm
28 fault types
4 Types
%
%
% or
O
C
%
1-9
Variable
Poll Mode
Programmed As
Actual Device
Device State
Device Status
LED Status
Alarm
Pre-alarm
Peak Alarm Value
Drift Compensation
Sensitivities
AFP-2800/2802 Manual
– P/N DOC-01-011