Panel Operation
7.3.3.7.2.1.1
Service Menu – List – List – Analog – Modules – Status – Test
This screen will perform functional tests on selected Analog addressable points. As modules can be both inputs
and outputs, there are two different modes of operation.
If module is an Input Module
Actions:
DAY MODE
20 JULY 2002 14:44:37
L1M1
(Z001) > BREAK GLASS ON PANEL
Poll Mode
> FlashScan Mode
Programmed As
> FMM-101-MMX-101 MINI MON
Actual Device
> FMM-101 MINI MON
Device State
> NORMAL
Device Status
> NORMAL
LED Status
> Polling
Press the
ALARM
button to perform an ALARM
TEST on the module.
Press the
FAULT
button to perform an FAULT
TEST on the module.
Press the
STATUS
button to return to the read
ALARM
FAULT
STATUS
If the module is an Output Module.
DAY MODE
20 JULY 2002 14:44:37
L1M10
> EWIS OUPUT #1
Poll Mode
> FlashScan Mode
Programmed As
> FRM-1/CMX-2 Relay O/P
Actual Device
> FMM-1 Relay
Device State
> NORMAL
Device Status
> NORMAL
LED Status
> Polling Green
USE BUTTONS TO SELECT TEST
.
OFF
Script processing is paused during an output module test. Scripts will automatically resume processing once
a test is complete.
AFP-2800/2802 Manual
– P/N DOC-01-011
40
•
Press the
ON
BUTTON TO TURN MODULE
LED’S ON
green (red if CLIP). (This test is useful for locating
detector/detectors at same address)
•
Press the
OFF
BUTTON TO RETURN MODULE LED
’S TO
the Automatic Polling Mode
•
•
USE BUTTONS TO SELECT TEST
.
•
ON
OFF
ANALOG MENU – TESTING
A = 0
F = 0
I = 0
N = 0
status screen.
Actions:
•
Press
ON
to activate the output module.
•
Press
OFF
to de-activate the output module.
•
Press
STATUS
to return to the read status
screen.
ON
Note:
STATUS
ANALOG MENU – TESTING
A = 0
F = 0
I = 0
N = 0