Panel Operation
7.3.7.1
S
ERVICE
M
ENU
–
G
LOBAL
–
S
YSTEM
This page displays system global parameters that can be toggled. The default states are shown below on the left,
while the toggled states are shown on the right.
Default Condition
Toggled Condition
DAY MODE
DAY MODE
20 JULY 2002 14:44:37
20 JULY 2002 14:44:37
SELECT A FUNCTION:
SELECT A FUNCTION:
FAULTS ARE NOT LATCHED
FAULTS ARE LATCHED
FF SCREEN ALARMS ARE SHOWN AS GROUPED ZONES
FF SCREEN ALARMS ARE SHOWN AS SINGLE POINTS
ZONE EVENTS NOT DISPLAYED IN SINGLE POINT MODE
ZONE EVENTS ARE DISPLAYED IN SINGLE POINT MODE
A/P/F/N LISTS AUTO SWITCHED
A/P/F/N LISTS MANUAL SWITCHED
ACTIVE LIST AUTO SWITCHED
ACTIVE LIST MANUAL SWITCHED
DISPLAY IMAGE IS NORMAL
DISPLAY IMAGE IS INVERTED
MODEM OPERATION IS DISABLED
MODEM OPERATION IS ENABLED
VIRTUAL POINTS NOT ADDED TO ACTIVE LIST
VIRTUAL POINTS ADDED TO ACTIVE LIST
PREALARM LOCAL SOUNDER ENABLED
PREALARM LOCAL SOUNDER DISABLED
WALK TEST GENERATES A FAULT IS ENABLED
WALK TEST GENERATES A FAULT IS DISABLED
NZ OPERATION MODE (NZS 4152) IS DISABLED
NZ OPERATION MODE (NZS 4152) IS ENABLED
GROUND FAULT REPORTING IS DISABLED
GROUND FAULT REPORTING IS ENABLED
OUTPUT ACTIVATION LOGGING IS DISABLED
OUTPUT ACTIVATION LOGGING IS ENABLED
AUTO RESET OF GROUP ISOLATES IS DISABLED
AUTO RESET OF GROUP ISOLATES IS ENABLED
UP
DOWN
TOGGLE
MENU
UP
DOWN
TOGGLE
MENU
Actions:
•
Use the
UP
and
DOWN
buttons to scroll through options and then use the
TOGGLE
button to select the
toggle the highlighted option. Changes are instant.
Explanation of Global Configuration Options:
Item
Description
Faults Latched / Non
Determines if faults will self clear or remain latched until a manual reset.
Latched
FF Screen shows individual
AS4428.1 has a requirement for Addressable points to show the zone to which
Alarms or group zones
they belong in the FF screen and not all the individual alarms. Please note that
when in this mode only the zone in alarm is displayed, if you want to know
which points are in alarm you must go to the service menu and view alarms.
When in group zone mode, a reset or isolate of a point mapped to a zone will
isolate / reset all points in the zone.
Zone events are displayed
In single point mode, this option allows the user to choose if the zone in alarm
in single point mode
is also displayed. I.e. Two events will be displayed for one device in alarm
–
the point in alarm and zone that the point is mapped to.
A/P/F/N Lists Manual
This setting determines if the panel should automatically jump to the alarm,
Switched or auto switched
pre-alarm, fault or non-alarm list if an alarm, pre-alarm, fault or non-alarm event
comes in and there are no alarms on the system. The panel will jump to the
event screen with the highest priority. The priority order is Alarm
Pre-alarm
Fault
Non-alarm.
Active List Switching
This disables auto switching of non-alarms (actives) if required.
Display image is normal or
This setting determines if the LCD display is black on white or white on black
inverted
(inverse).
Modem
Determines if the panel will support terminal mode using the PCI. Modem
operation must be enabled to use terminal mode with the PC Interface.
Virtual points are added /
This setting determines if active Virtual Points are added to the Non-alarm list.
AFP-2800/2802 Manual
– P/N DOC-01-011
76
SYSTEM CONFIGURATION
A = 0
F = 0
I = 0
N = 1
SYSTEM CONFIGURATION
A = 0
F = 0
I = 0
N = 1