12.  

Commissioning 

12.1 

Introduction 

The following equipment should be available where 
possible to minimise commissioning time: 

i)  VHF/UHF Portable Radio (for two engineers) 

ii)  Multi-meter or equivalent 

12.2 

Commissioning Checklist 

1.  Before  commissioning,  the  engineer  should 

check the following: 

i)  All field wiring has been inspected and tested 

in  accordance  with 

Manufacturer’s  wiring 

recommendations, 

current 

issues 

of 

BS5839:1 

and 

BS7671 

IEE 

wiring 

regulations. 

ii)  All  field  cables  are  glanded  into  the  control 

panel cabinet. 

iii)  Detector  bases  are  terminated  but  detector 

heads  are  not  fitted.  Any  devices  with 
electronic 

components 

are 

not 

fitted. 

Terminations  to  devices  with  electronic 
components  should  be  linked  through  to 
maintain cable continuity. 

iv) Manual  Call  Points  are  not  connected  but 

cable is linked through to maintain continuity. 

v)  No  end-of-line  devices  (e.g.  alarm  circuit 

EOL resistor) are fitted in the field. 

2.  The following  information should  be available  to 

the commissioning team: 

i)  Detection layout drawings. 

ii)  Wiring schematic diagram. 

iii)  Control Panel installation manuals. 

iv) Installation  manuals  for  all  equipment 

connected to the system. 

v)  Site specific configuration details. 

Experience  has  shown  that  tracing  wiring  faults 
on  long  circuits  that  are  routed  through  risers 
etc.  can  be  difficult  without  knowledge  of  the 
wiring route. 

It is recommended that the electrical installer be 
made  available  until  basic  wiring  continuity  is 
proven.  A  minimum  of  two  persons  (e.g. 
engineer and mate) is recommended for efficient 
commissioning. 

12.3 

Commissioning Procedure Overview 

Commissioning is broken in to 3 sections: 

i)  Pre-commissioning wiring check. 

ii)  Powering  the  panel  up  with  no  field  wiring 

connected,  configuring  the  panel  in  accordance 
with  the  site-specific  requirements  and  carrying 
out a functional check. 

iii)  Functional testing of all circuits and field devices 

to  check  each  circuit  and  function  in  turn  to 
ensure correct operation of the entire system. 

In  this  way  any  faults  may  be  located  quickly  and 
accurately. The general procedures are as follows: 

1.  Alarm  circuits  should  be  checked  first.  The 

correct  operation  of  each  sounder  should  be 
checked  for  correct  audibility  as  specified  in 
BS5839:1, using the Evacuate function.  

2.  Detection  zones  should  be  commissioned  next. 

The  purpose  is  to  establish  the  correct 
functioning  of  each  device  and  checking  for 
correct indication at the control panel. The panel 
responses  as  configured  should  be  checked  at 
this time. 

3.  All  ancillary  inputs  and  outputs  should  be 

commissioned and the functionality confirmed. 

4.  Fire protection signals should be tested. 

5.  Fire and fault routing signalling should be tested. 

WARNING: 

Before  testing,  the  engineer  must  be 

aware  both  of  the  operation  of  all  devices  fitted  to 
the  auxiliary  circuits  and  of  the  consequences  of 
their operation. 

12.4 

Pre-Commissioning Wiring Check 

NOTE:  This  pre-commissioning  wiring  check 
procedure  should  be  followed  to  test  all  wiring 
prior 

to 

specific 

commissioning 

of 

any 

detection, alarm and auxiliary circuits. 

1.  Ensure  that  no  devices  are  connected  to  the 

detection  zones  and  alarm  circuits,  but  that  the 
cables are linked through at the device locations 
to achieve a continuous circuit. 

2.  Ensure  that the  resistance  of  all  cables  to earth 

and between cores is at least 2M

Check the following: 

i)  Positive  to  earth  resistance  is  2M

Ω  or 

greater. 

ii)  Negative  to  earth  resistance  is  2M

Ω  or 

greater. 

iii)  Positive  to  negative  resistance  is  2M

Ω  or 

greater. 

3.  Connect a wire link as the end-of-line device on 

each  of  the  zones  and  alarm  circuits.  At  the 
panel  end,  measure  the  resistance  across  the 
positive  &  negative  ends  of  the  cables  for  each 
of  the  circuits;  ensuring  the  value  does  not 
exceed  20

Ω.  Remember  to  remove  the  wire 

links after the tests. 

Correct  polarity  throughout  all  circuits  must  be 
maintained. Rectify any faults. 

All  bells,  detector  heads  and  call  points  should 
now  be  connected  and  the  correct  end-of-line 
devices fitted. Use the spare end-of-line devices 
supplied and leave the EOL devices in the panel 

Summary of Contents for Precept EN 16

Page 1: ...PREC EN INST ISSUE No DATE 3 13 09 18 PAGE 1 of 30 Johnson Controls Tyco Fire Security GmbH Victor von Bruns Strasse 21 8212 Neuhausen am Rheinfall Switzerland Precept EN Fire Detection Alarm Panel P...

Page 2: ...15 4 ENGINEER S ZONE OUTPUT CONFIGURATION TIME OUT WARNING 23 15 5 INVALID CONFIGURATION CONDITIONS 23 15 6 LIST OF CONFIGURATION DIL SWITCHES AND THEIR FUNCTIONS 23 15 7 CONFIGURABLE OPTIONS VIA DIL...

Page 3: ...eps that are taken in designing installing and commissioning a FIRECLASS Precept EN system 1 Install all field wiring and equipment Refer to the Installation Guidelines in section 11 2 below Refer to...

Page 4: ...h label C1631 repeater interface optional J18 B Figure 3 Precept EN 32 Zone Internal View TB 1 30 J 1 J 1 TO MOTHERBOARD 25 TB 2 26 27 TB 3 18 17 19 TB 5 28 TB 4 29 TB 6 ZONE CIRCUITS 20 21 22 TB 8 31...

Page 5: ...EQUIPMENT FIRECLASS PRECEPT EN PUBLICATION FIRECLASS PREC EN INST ISSUE No DATE 3 13 09 18 PAGE 5 of 30 Figure 4 2 4 Zone Precept EN panel General Assembly with optional clock module...

Page 6: ...EQUIPMENT FIRECLASS PRECEPT EN PUBLICATION FIRECLASS PREC EN INST ISSUE No DATE 3 13 09 18 PAGE 6 of 30 Figure 5 8 16 Zone Precept EN panel General Assembly with optional clock module...

Page 7: ...EQUIPMENT FIRECLASS PRECEPT EN PUBLICATION FIRECLASS PREC EN INST ISSUE No DATE 3 13 09 18 PAGE 7 of 30 Figure 6 32 Zone Precept EN panel General Assembly with optional clock module...

Page 8: ...nnect to Aux DC 24V 24V DC relay Typical zonal output wiring Field relay spec Coil resistance 2 6K to 4 5K Ohms Voltage 24V DC Nom min 18V max 30V Fitted with suppression diode as shown Relay local to...

Page 9: ...A B GND Reset N C Inputs SIL Silence alarms EVAC Evacuate RST Reset Outputs DIS Disablement active EVAC Evacuation active BUZ Active Buzzer active Class change Buz Active Lower terminal tier Upper te...

Page 10: ...LED indicators OUTPUT OK Battery Charger Fault Charger Fault Mains Fault J18 Earth Fault Monitoring Link Secondary AC from transformer C1631 Repeater Interface Connector for C1632 Zone Expansion Board...

Page 11: ...denoting any one of the following conditions a Battery or associated wiring disconnected b Battery fuse blown c Low Battery voltage 15 7V 0 4V d Battery and interconnection resistance is equal to or...

Page 12: ...ne Panel Power Supply Layout Secondary AC Supply from Transformer 28V 0V DC Power output Mains Fault Output Common Fault Output 4 way header for connector to 32 zone motherboard for DC power common fa...

Page 13: ...care when lifting and transporting batteries For weights above 24 kilos lifting aids should be used DANGER Do NOT attempt to remove the battery lid or tamper with the internal workings of the battery...

Page 14: ...h contain PCBs with sensitive and fragile electronic components on them You must place them in an area that is clean dry and dust free where they will not be damaged You can place them inside the orig...

Page 15: ...igure 10 Figure 12 Fit the connector on the end of the black lead onto the negative black terminal of the left hand battery Fit the connector on the end of the red lead onto the positive red terminal...

Page 16: ...s and field devices to check each circuit and function in turn to ensure correct operation of the entire system In this way any faults may be located quickly and accurately The general procedures are...

Page 17: ...and the battery is OK the panel should be silent displaying only the Power Supply On indication 5 Turn the Access Keyswitch to 1 and press the Test Display button The panel should respond by lighting...

Page 18: ...ue to test each of the other detectors in turn checking on each removal that The appropriate amber zone fault LED illuminates The internal buzzer sounds The fault relay operates 5 Repeat steps 1 to 4...

Page 19: ...At Repeater 1 turn the Access control switch to 1 and press the Evacuate button Check that the alarms operate and the internal buzzer operates on all repeaters 3 Press the Silence button on the fire a...

Page 20: ...ult Disabled Yellow Flashes for a fault on the Fault Routing Output Steady when Fault Routing Output is disabled POWER SUPPLY ON FIRE FIRE ROUTING ACTIVE GENERAL FAULT POWER SUPPLY FAULT SYSTEM FAULT...

Page 21: ...and if silence before reset is configured sounders are silenced Silence Buzzer 1 Press to stop the buzzer sounding in fire or fault conditions Always available 2 In 2 Stage Delay Mode with stage 1 de...

Page 22: ...anel door to allow access to the buttons on the display 2 Select a zone or output to be configured o On the panel display press the Select On Off switch to enable the Select Mode The Select LED will b...

Page 23: ...onfig LED on the motherboard will flash o The System Fault and Select LEDs on the display will flash o The fault relay will operate o The panel buzzer will sound o The Cursor indication will clear o C...

Page 24: ...es Sets the duration of the variable time delay element i e the single stage delay and stage 2 of the two stage delay in steps of 1 minute within the range 0 9 minutes See Table 1 Motherboard Delay Sw...

Page 25: ...ff Off On 5 On Off On Note Address 0 repeater disabled 15 8 Configuring the Fire Routing Fire Protection and Fault routing O Ps To configure the Fire Routing Output to volt free relay contacts remove...

Page 26: ...DISABLE to change MM to desired value 00 to 59 Press SELECT ON Time Set display HH MM SS ON Time SS flashing Press ENABLE or DISABLE to change SS to desired value 00 to 59 To set Day Night Mode Off Ti...

Page 27: ...Settings LINK 1 Position Function Fitted 1st fire alarm time display mode Removed Day Night mode Link 1 DIL Switch 1 DIL Switch Position Function Off 1 Off Clock Module menu configuration disabled 1...

Page 28: ...ulses every second WP DILSW IS ON The backlight remains OFF The panel indicates a general fault and prevents the clock module from being accessed by the user engineer 16 4 2 EEPROM Error Message Data...

Page 29: ...250V 1A anti surge T1A H250V 1A anti surge T1A H250V 1A anti surge Voltage 230V AC 10 15 Cable requirements Minimum of 1mm2 copper protected by a 5A fuse Power Supply Output Specification Precept EN P...

Page 30: ...ff PS1230 2V 3 4Ah 2 off PS1230 12V 3 4Ah Battery size mm L HT H W L 133 W 67 H 60 HT 66 L 151 W 65 H 94 HT 98 L 151 W 98 H 94 HT 100 L 181 W 76 H 167 HT 167 L 133 W 67 H 60 HT 66 L 133 W 67 H 60 HT 6...

Reviews: