background image

EQUIPMENT:

 

 

FIRE

CLASS 

PRECEPT EN 

 

 

 

WRITTEN BY: RKP 

PUBLICATION:

  

FIRECLASS PREC EN OUTPUT EXP MOD INST 

CHECKED BY: AP 

ISSUE No. & DATE:

 

0      02/03/12

 

PAGE 3 of 21 

1. Introduction 

This  document  contains  all  the  information 
necessary  for  the  installation,  commissioning  and 
maintenance  of  the 

FIRE

CLASS

  Precept  EN

 

range 

of  output  expansion  panels.  Installation  and 
commissioning details for Precept EN fire detection 
and  alarm  panels  are  covered  in  the 

FIRE

CLASS

 

Precept EN manuals mentioned below. 

NOTE:  It  is  important  to  read  this  manual  fully 

before commencing installation. 

The  following  supporting  documentation  is  also 
available: 

 

FIRE

CLASS

  Precept  EN

 

Output  Expansion 

System Application Guide 

 

FIRE

CLASS

  Precept  EN  Panel  Application 

Guide 

 

FIRE

CLASS

 Precept EN

 

User Manual 

  Wiring Recommendations 

2. Overview of Installation and 

Commissioning 

This  section  lists  the  steps  that  are  taken  in 
installing  and  commissioning  a  Precept  EN

 

output 

expansion system. 

1.  Install all field wiring and equipment 

  Refer  to  the  Installation  Guidelines  in  section 

6.2 below 

  Refer to the field device installation manuals 

2.  Install the panel 

  Refer  to  the  installation  instructions  in  section 

6.2 below 

  Do  not  connect  the  field  equipment  at  this 

stage. 

3.  Commission the panel 

  Refer to section 6.  

3. Power Supplies 

The 

FIRE

CLASS

  Precept  EN  8-Zone  fire  alarm 

panel utilises the standard 230Vac 3A PSU fitted to 
the  C1627  motherboard.  The 

FIRE

CLASS

  Precept 

EN 16L fire alarm panel uses the C1652 230Vac 5A 
PSU  mounted  on  the  internal  chassis  beneath  the 
motherboard  &  output  modules. 

FIRE

CLASS

 

Precept  EN  Exp  4  and  5  output  expansion  panels 
are  supplied  with  or  without  a  C1652  230Vac  5A 
PSU  depending  on  the  output  load  requirement. 
When  fitted,  the  PSU  is  located  on  the  chassis 
underneath the output modules. 
For all panels, the output voltage is adjustable from 
25Vdc to 28.2Vdc via a small trimmer potentiometer 
on  the  PCB.  As  the  output  voltage  is  factory  set 
however, adjustment should not be necessary. 
Details of the PSUs can be found in the 

FIRE

CLASS

 Precept EN manuals. 

4. Output Module Field 

Wiring/Terminal Diagrams 

Figure 1 

– C1633 Field Wiring Connections 

2

k

2

 0

.5

W

 

re

s

is

to

r

C1633 Open collector output  module terminals

Typical LED indication wiring

Max current sink into O/P: 60mA

Max load on 24V [total for both 

+24V O/Ps]: 0.5A

+

2

4

V

+

2

4

V

O

P

1

O

P

2

O

P

3

O

P

4

O

P

5

O

P

6

O

P

7

O

P

8

 

Figure 2 

– C1634 Field Wiring Connections 

Lower 

terminal 

tier

Middle 

terminal 

tier

Upper 

terminal 

tier

C1634 Volt free relay output  module 

terminals [3- tier]

Relay contact rating: 1A at 30Vdc

Do not exceed 

OP1 OP2 OP3 OP4 OP5 OP6 OP7 OP8

N

/C

N

/O

P

O

L

E

 

Figure 3 

– C1635 Field Wiring Connections 

+ OP1 -

+ OP2 -

+ OP3 -

+ OP4 -

+ OP5 -

+ OP6 -

+ OP7 -

+ OP8 -

Lower 

terminal 

tier

Upper 

terminal 

tier

C1635 powered/fault monitored 

output  module terminals [2- tier]

3k9 resistor

end-of-line

Typical Alarm 

Circuit  Wiring

I/P polarised

[All sounder 

devices]

3k9 resistor

end-of-line

Typical Remote 

Relay Circuit 

Wiring

Suppression diode

Polarising diode

+

+

-

-

+

+

-

-

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for Precept EN Panel

Page 1: ...PAGE 1 of 21 Precept EN Output Expansion Module Installation Commissioning Manual www acornfiresecurity com www acornfiresecurity com...

Page 2: ...1634 FIELD WIRING CONNECTIONS 3 FIGURE 3 C1635 FIELD WIRING CONNECTIONS 3 FIGURE 4 PRECEPT EN 16 INTERNAL VIEW SHOWING OPTIONAL SINGLE O P BOARD 4 FIGURE 5 PRECEPT EN 16L INTERNAL VIEW 32 ZONE ENCLOSU...

Page 3: ...The FIRECLASS Precept EN 16L fire alarm panel uses the C1652 230Vac 5A PSU mounted on the internal chassis beneath the motherboard output modules FIRECLASS Precept EN Exp 4 and 5 output expansion pane...

Page 4: ...mary Earth Connection Removable Chassis Relay output Module Batteries Motherboard C1630 Output Expansion Interface Board Removable Chassis Figure 5 Precept EN 16L internal view 32 zone enclosure with...

Page 5: ...Exp 5 internal view Mains Warning Primary Earth Label Cable Clip for incoming mains cable 3 x Enclosure fixing holes Secondary Earth bars for cable screens Mains Terminal Block and primary Earth Conn...

Page 6: ...ake great care when lifting and transporting batteries For weights above 24 kilos lifting aids should be used DANGER Do NOT attempt to remove the battery lid or tamper with the internal workings of th...

Page 7: ...rol panel remove the chassis from the output expansion panel generally as described in the FIRECLASS Precept EN panel installation manual carefully remove the 25mm knock outs in the adjoining faces of...

Page 8: ...bbon Motherboard C1627 connector J17 Connector J2 on O P module 1 left hand most module Figure 15 Aux DC power cable Motherboard C1627 power out connector J24 Power in connector on the first C1633 C16...

Page 9: ...1635 8 zone with 1 O P module Exp 4 or Exp5 with power supply Data Ribbon Data out connector on the O P module J6 on C1633 and C1635 Connector J2 on O P module 1 left hand most module Figure 16 Aux DC...

Page 10: ...fit a C1630 output expansion interface to connectors J4 and J5 see Figure 7 J21 must be removed before the interface board can be fitted The board should be held in place by the 12mm high plastic spac...

Page 11: ...ctional All O Ps operate on any zonal fire On Off Off Z 1 8 On On Off Z9 16 On Off On Z17 24 On On On Z25 32 C1633 Connectors J1 Programming header J2 Comms to panel motherboard J3 Power out J4 Power...

Page 12: ...er Marine Panels only C1634 Connectors J1 Programming header J2 Comms and power from panel motherboard Figure 9 C1634 PCB Layout ZONAL ZN1 ZN0 AD1 AD0 1 2 3 4 5 SW1 J3 J2 SW2 PROC FAULT RESET COMS FLT...

Page 13: ...n FP N A On On Off Z9 16 On FP N A On Off On Z17 24 On FP N A On On On Z25 32 Notes SNDR Sounders FP Fire Protection When panel SW 2 6 is on If panel SW2 7 is off non alarm zones are silent If panel S...

Page 14: ...and any subsequent sounder circuits 7 2 2 Powered fault monitored Fire Protection outputs C1635 modules configured as Fire Protection O Ps 1 Ensure any fire protection equipment to be controlled via...

Page 15: ...one to operate the output and check that the output does not operate Reset the panel and re enable the Fire Protection O Ps after the test 6 Final testing and commissioning of the loop through to the...

Page 16: ...4 way O P enclosure with max 4 O P modules with or without optional 5 Amp PSU and batteries 5 Precept EN 32 with Exp 5 5 way O P enclosure with max 5 O P modules with or without optional 5 Amp PSU an...

Page 17: ...ith max 5 O P modules with or without optional 5 Amp PSU and batteries C1634 J2 Data ribbon Aux DC J17 J24 C1627 Motherboard Precept EN Exp 4 4 way O P expansion enclosure with 4 modules powered from...