6.2  Installation Instructions 

The  flexibility  of  the  Precept  EN  Output  Expansion 
System  allows  many  different  combinations  of 
enclosure/PSU/output  modules.  As  such  these 
instructions cannot cover every single variation and 
so provide general instructions only. 

1.  Carefully remove the panel from the packing and 

lay the panel on a flat surface. 

2.  Open the door of the panel. 

3.  Locate  the  spares  bag[s]  and  check  contents, 

which  should  comply  with  Table  1 

–  Panel 

Spares Bag Contents. 

6.2.1  Precept EN 16 Exp Panel 

Installation Instructions 

See  the 

FIRE

CLASS

  Precept  en  panel  installation 

manual. 

6.2.2  Precept EN 4 and 5 Exp 

Expansion Enclosures 

Matching  25mm  knock-outs  are  provided  on  the 
right  hand  face  of  the  Precept  EN  8/16  fire  alarm 
panel  enclosure  and  the  left  hand  face  of  the 
Precept  EN  4  Exp  output  expansion  enclosure  to 

allow  the  panels  to  be  coupled  together  with  the 
expansion panel on the right. A similar arrangement 
is  provided  for  connecting  Precept  EN  32  control 
panels to the Precept EN 5 Expansion enclosure. 

Mount  and  fix  the  fire  alarm  panel  enclosure  in 
accordance  with  the  instructions  provided  in  the 

FIRE

CLASS

 Precept EN panel installation manual. 

After fitting the fire alarm control panel, remove the 
chassis  from  the  output  expansion  panel  generally 
as  described  in  the 

FIRE

CLASS

  Precept  EN  panel 

installation  manual,  carefully  remove  the  25mm 
knock-outs  in  the  adjoining  faces  of  both  fire  panel 
and  expansion  enclosures  [by  knocking  out  from 
the  inside  of  the  enclosure  to the  outside] and  fit  a 
25mm coupler to one panel. Offer up the expansion 
box,  aligning  the  two  enclosures  via  the  coupler 
then  mark.  Fix  the  expansion  enclosure  to  the  wall 
as  described  in  the 

FIRE

CLASS

  Precept  EN  panel 

installation  manual.  Tighten  up  the  coupler. 
Continue  to  install  in  accordance  with  the  relevant 
guidelines provided in the 

FIRE

CLASS

 Precept EN 

panel  installation  manual  as  appropriate  to  the 
output expansion module system provided. 

 

 

Table 1 

– Panel Spares Bag Contents 

Panel 

Spares Bag 

Panel

 

Expansion Modules [as fitted] 

C1633 

C1634 

C1635 

[1 bag per module] 

Precept EN 8 & 

16 zone 

panel with 

optional O/P 

module 

See 

FIRE

CLASS

 Precept EN 

installation and commissioning manual 

None 

required 

None 

required 

8 x 3k9 0.25W 

Precept EN 16L 

See 

FIRE

CLASS

 Precept EN 

installation and commissioning manual 

None 

required 

None 

required 

8 x 3k9 0.25W 

Exp 4 or 5 

[no PSU] 

Engineer’s door keys. Key Ref.: 

801 [Flat key type] 

None 

required 

None 

required 

8 x 3k9 0.25W 

Exp 4 or 5 

[C1652 PSU] 

Mains Fuse: 

T3.15AH250V 

20mm 

None 

required 

None 

required 

8 x 3k9 0.25W 

Battery Fuse: 

F6.3AL250V 

20mm 

Engineer’s door 

keys: 

Key Ref.: 

801 [Flat key 

type] 

Positive battery 

lead: 

Red 

Negative battery 

lead: 

Black 

Battery coupling 

lead: 

Blue 

 

 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for Precept EN Panel

Page 1: ...PAGE 1 of 21 Precept EN Output Expansion Module Installation Commissioning Manual www acornfiresecurity com www acornfiresecurity com...

Page 2: ...1634 FIELD WIRING CONNECTIONS 3 FIGURE 3 C1635 FIELD WIRING CONNECTIONS 3 FIGURE 4 PRECEPT EN 16 INTERNAL VIEW SHOWING OPTIONAL SINGLE O P BOARD 4 FIGURE 5 PRECEPT EN 16L INTERNAL VIEW 32 ZONE ENCLOSU...

Page 3: ...The FIRECLASS Precept EN 16L fire alarm panel uses the C1652 230Vac 5A PSU mounted on the internal chassis beneath the motherboard output modules FIRECLASS Precept EN Exp 4 and 5 output expansion pane...

Page 4: ...mary Earth Connection Removable Chassis Relay output Module Batteries Motherboard C1630 Output Expansion Interface Board Removable Chassis Figure 5 Precept EN 16L internal view 32 zone enclosure with...

Page 5: ...Exp 5 internal view Mains Warning Primary Earth Label Cable Clip for incoming mains cable 3 x Enclosure fixing holes Secondary Earth bars for cable screens Mains Terminal Block and primary Earth Conn...

Page 6: ...ake great care when lifting and transporting batteries For weights above 24 kilos lifting aids should be used DANGER Do NOT attempt to remove the battery lid or tamper with the internal workings of th...

Page 7: ...rol panel remove the chassis from the output expansion panel generally as described in the FIRECLASS Precept EN panel installation manual carefully remove the 25mm knock outs in the adjoining faces of...

Page 8: ...bbon Motherboard C1627 connector J17 Connector J2 on O P module 1 left hand most module Figure 15 Aux DC power cable Motherboard C1627 power out connector J24 Power in connector on the first C1633 C16...

Page 9: ...1635 8 zone with 1 O P module Exp 4 or Exp5 with power supply Data Ribbon Data out connector on the O P module J6 on C1633 and C1635 Connector J2 on O P module 1 left hand most module Figure 16 Aux DC...

Page 10: ...fit a C1630 output expansion interface to connectors J4 and J5 see Figure 7 J21 must be removed before the interface board can be fitted The board should be held in place by the 12mm high plastic spac...

Page 11: ...ctional All O Ps operate on any zonal fire On Off Off Z 1 8 On On Off Z9 16 On Off On Z17 24 On On On Z25 32 C1633 Connectors J1 Programming header J2 Comms to panel motherboard J3 Power out J4 Power...

Page 12: ...er Marine Panels only C1634 Connectors J1 Programming header J2 Comms and power from panel motherboard Figure 9 C1634 PCB Layout ZONAL ZN1 ZN0 AD1 AD0 1 2 3 4 5 SW1 J3 J2 SW2 PROC FAULT RESET COMS FLT...

Page 13: ...n FP N A On On Off Z9 16 On FP N A On Off On Z17 24 On FP N A On On On Z25 32 Notes SNDR Sounders FP Fire Protection When panel SW 2 6 is on If panel SW2 7 is off non alarm zones are silent If panel S...

Page 14: ...and any subsequent sounder circuits 7 2 2 Powered fault monitored Fire Protection outputs C1635 modules configured as Fire Protection O Ps 1 Ensure any fire protection equipment to be controlled via...

Page 15: ...one to operate the output and check that the output does not operate Reset the panel and re enable the Fire Protection O Ps after the test 6 Final testing and commissioning of the loop through to the...

Page 16: ...4 way O P enclosure with max 4 O P modules with or without optional 5 Amp PSU and batteries 5 Precept EN 32 with Exp 5 5 way O P enclosure with max 5 O P modules with or without optional 5 Amp PSU an...

Page 17: ...ith max 5 O P modules with or without optional 5 Amp PSU and batteries C1634 J2 Data ribbon Aux DC J17 J24 C1627 Motherboard Precept EN Exp 4 4 way O P expansion enclosure with 4 modules powered from...

Page 18: ...ulation must be carried out for each application Aux DC TB1 28V 0V MFlt CFlt TB5 J1 PWR Flt O Ps C1652 5 Amp PSU Aux DC Mains Flt Comm PSU Flt Aux DC or use additional PSU J2 C1635 J6 J2 C1635 J6 Note...

Page 19: ...s Data ribbon Precept EN 32 with 5 Amp PSU Precept EN Exp 5 5 way O P expansion enclosure C1627 Precept EN Motherboard Aux DC Further expansion modules PSU load calculation must be carried out for eac...

Page 20: ...re with 4 modules powered from the Precept EN panel Aux DC Note All C1634 modules must be connected at the end of the sequence J2 C1633 J6 J4 J3 J2 C1633 J6 J4 J3 J2 C1635 J6 J3 J5 J3 C1634 J2 J3 Aux...

Reviews: