EQUIPMENT:
FIRE
CLASS
PRECEPT EN
WRITTEN BY: RKP
PUBLICATION:
FIRECLASS PREC EN OUTPUT EXP MOD INST
CHECKED BY: AP
ISSUE No. & DATE:
0 02/03/12
PAGE 7 of 21
6.2 Installation Instructions
The flexibility of the Precept EN Output Expansion
System allows many different combinations of
enclosure/PSU/output modules. As such these
instructions cannot cover every single variation and
so provide general instructions only.
1. Carefully remove the panel from the packing and
lay the panel on a flat surface.
2. Open the door of the panel.
3. Locate the spares bag[s] and check contents,
which should comply with Table 1
6.2.1 Precept EN 16 Exp Panel
Installation Instructions
See the
FIRE
CLASS
Precept en panel installation
manual.
6.2.2 Precept EN 4 and 5 Exp
Expansion Enclosures
Matching 25mm knock-outs are provided on the
right hand face of the Precept EN 8/16 fire alarm
panel enclosure and the left hand face of the
Precept EN 4 Exp output expansion enclosure to
allow the panels to be coupled together with the
expansion panel on the right. A similar arrangement
is provided for connecting Precept EN 32 control
panels to the Precept EN 5 Expansion enclosure.
Mount and fix the fire alarm panel enclosure in
accordance with the instructions provided in the
FIRE
CLASS
Precept EN panel installation manual.
After fitting the fire alarm control panel, remove the
chassis from the output expansion panel generally
as described in the
FIRE
CLASS
Precept EN panel
installation manual, carefully remove the 25mm
knock-outs in the adjoining faces of both fire panel
and expansion enclosures [by knocking out from
the inside of the enclosure to the outside] and fit a
25mm coupler to one panel. Offer up the expansion
box, aligning the two enclosures via the coupler
then mark. Fix the expansion enclosure to the wall
as described in the
FIRE
CLASS
Precept EN panel
installation manual. Tighten up the coupler.
Continue to install in accordance with the relevant
guidelines provided in the
FIRE
CLASS
Precept EN
panel installation manual as appropriate to the
output expansion module system provided.
Table 1
– Panel Spares Bag Contents
Panel
Spares Bag
Panel
Expansion Modules [as fitted]
C1633
C1634
C1635
[1 bag per module]
Precept EN 8 &
16 zone
panel with
optional O/P
module
See
FIRE
CLASS
Precept EN
installation and commissioning manual
None
required
None
required
8 x 3k9 0.25W
Precept EN 16L
See
FIRE
CLASS
Precept EN
installation and commissioning manual
None
required
None
required
8 x 3k9 0.25W
Exp 4 or 5
[no PSU]
Engineer’s door keys. Key Ref.:
801 [Flat key type]
None
required
None
required
8 x 3k9 0.25W
Exp 4 or 5
[C1652 PSU]
Mains Fuse:
T3.15AH250V
20mm
None
required
None
required
8 x 3k9 0.25W
Battery Fuse:
F6.3AL250V
20mm
Engineer’s door
keys:
Key Ref.:
801 [Flat key
type]
Positive battery
lead:
Red
Negative battery
lead:
Black
Battery coupling
lead:
Blue