background image

EQUIPMENT:

   

FIRE

CLASS 

PRECEPT EN13

 

PUBLICATION:

  

FIRECLASS PREC EN13 INST

 

ISSUE No. & DATE:

 

2     22/07/2021

 

PAGE 13 of 32 

10.2  Installation Instructions 

1.  Carefully remove the control panel from the 

packing and lay the panel on a flat surface. 

2.  Open the door of the panel. 
3.  Locate the spares bag and check that the 

following items are present: 

Item 

Precept EN13

 

2/4 

Precept EN13 

8/16 

Mains Fuse 

T1AH250V 

20mm 

1 off 

T3.15AH250V 

20mm 

1 off 

Battery Fuse 

F2AL250V 

20mm 

1 off 

F5AL250V 

20mm [8/16] 

EOL 

capacitor/resistor 

device for normal 

zone monitoring 

22μF

/3k9 

2/4 off 

22μF

/3k9 

8/16 off 

EOL resistors for 

I.S. zones. 

3k9 0.25W 

2/4 off 

3k9 0.25W 

8/16 off 

Engineer’s door 

keys 

Key Ref.: 

801 [Flat] 

1 off 

Key Ref.: 

801 [Flat] 

1 off 

Access Control 

keys 

Key Ref.: 

801 [Tubular] 

1 off 

Key Ref.: 

801 [Tubular] 

1 off 

Positive battery 

lead 

Red 

1 off 

Red 

1 off 

Negative battery 

lead 

Black 

1 off 

Black 

1 off 

Battery coupling 

lead 

Blue 

1 off 

Blue 

1 off 

10.2.1  Panel Installation Instructions 

1.  Disconnect the display ribbon cable from the 

motherboard header. 

2.  Disconnect the earth strap connecting the door 

and backbox via the spade terminal on the door. 

3.  Unscrew the hinge pin at the bottom of the door 

whilst supporting the door. Swing the bottom of 

the door clear of the backbox and pull the door 

away from the top hinge pin. 

4.  Place the door carefully to one side and replace 

the bottom hinge pin in the backbox. 

5.  Unscrew and remove the two lower chassis 

screws and 

only slacken

 the top two mounting 

screws. 

6.  Carefully lift the chassis upward to align the 

screw heads with the large holes in the chassis 

keyholes. Lift the chassis clear of the upper 

screws and rest the chassis in the bottom of the 

enclosure. Take care not to strain the wires that 

remain connected to the backbox. 

7.  Disconnect the earth strap connecting the 

backbox and chassis at the earth bar. 

8.  Disconnect the flying leads from the transformer 

to the mains terminal block and earth bar. 

9.  Remove the chassis from the enclosure and 

place carefully to one side. 

NOTE: The door and chassis both contain 

PCBs with sensitive and fragile electronic 

components on them. You must place them 

in  an area that is clean, dry and dust-free, 

where they will not be damaged. You can 

place them inside the original packing box 

but you must ensure that sufficient soft 

packing is used to keep the door and chassis 

separated. 

10. Identify the three indented holes in the backbox 

that are used to mount the enclosure. 

11. Place the enclosure in the desired location and 

mark the position of the top indented hole. 

Remove the enclosure and fit a suitable fixing to 

the wall. Hang the enclosure from the top fixing 

point and ensure that it is level. Mark the 

locations of the other two mounting holes. 

12. Remove the enclosure from the wall and fit 

suitable fixings to the two remaining mounting 

points. Fix the enclosure to the wall using all 

three mounting points. 

13. Carefully remove the required knock-outs in the 

panel enclosure and gland all field wiring in 

place ensuring that the cable conductors are of 

sufficient length inside the enclosure. Ensure 

that all conductors are clearly labelled. 

DO NOT 

remove knock-outs from any unused cable 

entries. Any unused cable entries which are 

open must be sealed with a suitable plug 

(available separately).

 

14. Connect the earth drain wires of the field cabling 

to the brass earth bar positioned at the top of the 

backbox. Up to two drain wires may be 

connected to each terminal.  

15. Ensure that continuity of any cable shield is 

maintained through to the last device on the 

circuit.  The shield must only be connected to 

enclosure earth in the panel by using the earth 

bars provided. [Different requirements apply for 

the screen of data cable used for connecting 

repeaters - see 10.2.2 below]

16. Connect the incoming protective earth conductor 

to the Earth terminal in the mains terminal block. 

This is the primary earth point and is labelled Í  

[also labelled E]. See Section 0 

17. Clear any dust and debris from inside the 

enclosure. 

18. Connect the mains-in Live cable to the mains 

terminal block [L terminal] as indicated in section 

19. Connect the mains-in Neutral cable to the mains 

terminal block [N terminal] as indicated in 

section 0 

20. Secure the mains-in cable to the cable clamp 

adjacent the mains terminal using the cable tie 

supplied. NOTE: The clamp should be over the 

outer cable insulation. 

21. Reinstallation of the chassis is the reverse of 

removal. Reconnect all wires and ensure none 

Summary of Contents for Precept EN13

Page 1: ...UIPMENT FIRECLASS PRECEPT EN13 PUBLICATION FIRECLASS PREC EN13 INST ISSUE No DATE 2 22 07 2021 PAGE 1 of 32 Precept EN13 Fire Detection Alarm Panel Precept EN Repeater Installation Commissioning Manua...

Page 2: ...RY DEFAULT CONFIGURATION FOR ZONES OUTPUTS 22 14 4 ENGINEER S ZONE OUTPUT CONFIGURATION TIME OUT WARNING 22 14 5 INVALID CONFIGURATION CONDITIONS 22 14 6 LIST OF CONFIGURATION DIL SWITCHES AND THEIR F...

Page 3: ...this manual fully before commencing installation The following supporting documentation is also available FIRECLASS Precept EN13 Sales Literature FIRECLASS Precept EN13 Panel Application Guide FIRECLA...

Page 4: ...3 2 1 ZONE CIRCUITS RST SIL EVAC CLASS CHANGE BUZ ACTIVE P A B REPEATER AUX D C 0V OUTPUTS INPUTS EVAC FAULT GND O ZONE OUTPUTS 4 3 2 1 24V 0V 2 1 3 01 05 12 ISSUE 0 CEL C1717 ALARM 4 3 2 1 CIRCUITS...

Page 5: ...ACKBOX N L M a in s F u s e R ep la ce Sa m e Ty pe W ith RATING LABEL EARTH POST EARTH BAR MAINS TERMINAL ASSEMBLY RELAY BOARD Fu se In pu t Se ria l N o Pa rt N o Pr od uc t St an da rd s A pp ro va...

Page 6: ...EQUIPMENT FIRECLASS PRECEPT EN13 PUBLICATION FIRECLASS PREC EN13 INST ISSUE No DATE 2 22 07 2021 PAGE 6 of 32 Figure 4 8 16 Zone Precept EN13 panel General Assembly with optional clock module...

Page 7: ...iagram Connect to Aux DC 24V 24Vdc relay Typical zonal output wiring Field relay spec Coil resistance 2 6k to 4 5k Ohms Voltage 24Vdc Nom min 18V max 30V Fitted with suppression diode as shown Relay f...

Page 8: ...les from Panel motherboard Each Alarm circuit from the panel motherboard is connected to the IN terminals on the Alarm Relay Board Each Alarm Circuit is wired out to the sounders from the OUT terminal...

Page 9: ...le on selected panel Alarm Circuits 1 2 3 4 Aux DC 24V 0V SIL Inputs Outputs Repeater EVAC RST DIS EVAC A B GND Reset N C Inputs SIL Silence alarms EVAC Evacuate RST Reset Outputs DIS Disablement acti...

Page 10: ...Terminals Power Supply LED indicators OUTPUT OK Battery Charger Fault Charger Fault Mains Fault J18 Earth Fault Monitoring Link Secondary AC from transformer C1631 Repeater Interface Alarm Circuits Ma...

Page 11: ...tion resistance is greater than or equal to 1 the Batt Charge fault LED is illuminated and the Fault Output is operated The circuitry also protects against reversed connection of the batteries 9 2 Vis...

Page 12: ...eat care when lifting and transporting batteries For weights above 24 kilos lifting aids should be used DANGER Do NOT attempt to remove the battery lid or tamper with the internal workings of the batt...

Page 13: ...n an area that is clean dry and dust free where they will not be damaged You can place them inside the original packing box but you must ensure that sufficient soft packing is used to keep the door an...

Page 14: ...y 26 Connect the blue battery lead between the positive red terminal of the left hand battery and the negative black terminal of the right hand battery Note that the batteries will not power the panel...

Page 15: ...should be checked for correct audibility as specified in BS5839 1 using the Evacuate function 2 Detection zones should be commissioned next The purpose is to establish the correct functioning of each...

Page 16: ...ise the mains and check the voltage and polarity are correct before replacing the panel fuse 4 The panel will power up and enter the power up cable check mode flashing System Fault LED After about 60...

Page 17: ...nearest the panel operate each manual call point and detection device on the zone in turn o After operation of each device confirm The fire indication is provided on the panel on the correct zone The...

Page 18: ...ed out at the appropriate time in conjunction with the engineer responsible for the fire protection system 11 7 6 Ancillary inputs Remote Silence Alarms Reset and Evacuate inputs should each be tested...

Page 19: ...isabled Fault Routing Fault Disabled Yellow Flashes for a fault on the Fault Routing Output Steady when Fault Routing Output is disabled POWER SUPPLY ON FIRE FIRE ROUTING ACTIVE GENERAL FAULT POWER SU...

Page 20: ...ked and if silence before reset is configured sounders are silenced Silence Buzzer 1 Press to stop the buzzer sounding in fire or fault conditions Always available 2 In 2 Stage Delay Mode with stage 1...

Page 21: ...and the panel buzzer will silence A pulsing indication cursor will appear either on the Zone 1 Fault Disabled LED or the Sounder Fault Disabled LED Test depending upon which configuration DIL switch i...

Page 22: ...e o The panel buzzer will sound o The Cursor indication will clear o Configuration will be inhibited To clear the invalid condition check the configuration switches SW1 4 to SW1 8 on the motherboard a...

Page 23: ...1 minute within the range 0 9 minutes See Table 1 Motherboard Delay Switch Settings Table 1 Motherboard Delay Switch Settings Delay Duration SW2 2 SW2 3 SW2 4 SW2 5 NONE Off Off Off Off 1 minute On Of...

Page 24: ...14 8 Configuring the Fire Routing Fire Protection and Fault routing O Ps To configure the Fire Routing Output to volt free relay contacts remove links J10 J11 and J12 These links are combined in a sin...

Page 25: ...to 59 Press SELECT ON Time Set display HH MM SS ON Time SS flashing Press ENABLE or DISABLE to change SS to desired value 00 to 59 To set Day Night Mode Off Time Press SELECT to access day night OFF...

Page 26: ...or EEPROM1 EEPROM 0 ERROR or EEPROM 1 ERROR Note Both EEPROMs can be erased by the following procedure 1 Power the panel down 2 Place the WP DIL switch in the ON position 3 Power the panel back up 4...

Page 27: ...15 4 C1651 Clock Module PCB Features Figure 10 llustrates the PCB features referred to elsewhere in the documentation Figure 10 C1651 Clock Module PCB LK1 Select Operating Mode LK1 S1 WP ZERO 1 2 ON D...

Page 28: ...Voltage 230Vac 10 15 Cable requirements Minimum of 1mm2 copper protected by a 5A fuse Power Supply Output Specification Panel Repeater AC powered 2 4 zone 8 zone 16 zone 2 4 8 16 zone Maximum Short T...

Page 29: ...off PS12120 12V 12Ah 2 off PS12120 12V 12Ah 2 off PS12120 12V 12Ah 2 off PS1230 12V 3 4Ah Battery size mm L HT H W L 151 W 98 H 94 HT 100 L 151 W 98 H 94 HT 100 L 151 W 98 H 94 HT 100 L 133 W 67 H 60...

Page 30: ...characteristics Performance under fire conditions Pass Response delay response time to fire Pass Operational reliability Pass Durability of operational reliability Temperature resistance Pass Durabil...

Page 31: ...5 EN BSEN 54 4 Power supply equipment for fire detection and fire alarm systems for buildings List of essential characteristics Performance under fire conditions Pass Operational reliability Pass Dura...

Page 32: ...2 07 2021 2021 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice Tyco Fire Security...

Reviews: