background image

EQUIPMENT:

   

FIRE

CLASS 

PRECEPT EN13

 

PUBLICATION:

  

FIRECLASS PREC EN13 INST

 

ISSUE No. & DATE:

 

2     22/07/2021

 

PAGE 16 of 32 

All bells, detector heads and call points should 

now be connected and the correct end-of-line 

devices fitted to the zone circuits. Use the spare 

end-of-line devices supplied and leave the EOL 

devices in the panel terminals at this stage. 

Remember to remove any links fitted to detector 

bases. The EOL resistor for the alarm circuits is 

already fitted to the Alarm Circuit Relay Board 

inside the panel. Be very careful to maintain 

correct polarity at each device. 

Warning: Intrinsically safe zone arrangement. 

 

The capacitor/resistor EOL  cannot be 

connected to zones monitoring Intrinsically 

Safe detection devices in hazardous areas. 

To do so will risk causing an explosion in the 

hazardous area. End-of-line resistors with a 

value of 3k9 must be used, which comply 

with the requirements laid down in the 

installation data sheets provided with the I.S. 

barrier and the I.S. fire detection devices. 

 

In order for detector head removal 

monitoring to function correctly when 

resistors are used as the end-of-line devices, 

any diodes in the detector bases that are in 

circuit when the detector head is removed 

must be disconnected. 

 

The panel must be configured to monitor 

Intrinsically Safe zones. 

 

The first device on an Intrinsically Safe zone 

must be a  MTL5561  Galvanic Isolator. 

Detectors and Manual Call Points on the Safe 

side of the barrier are not permitted. 

 

To comply with the requirements of BS5839, 

all manual call points should be located in 

the zone cabling between the I.S. 

Barrier/Isolator and the first detector. Any 

manual call point or detector located on the 

“end-of-line” side of a detector will be 

rendered inoperative if a  detector head is 

removed. 

11.5  Powering up 

1.  Prior to powering up, the panel will have been 

installed in accordance with the installation 

instructions, all cabling will have been fully 

installed and tested, glanded into the panel 

enclosure but not connected to the panel 

terminals. The mains supply should be isolated 

externally to the panel. 

2.  Check the battery connections are correct. 
3.  Remove the mains supply fuse from the panel 

mains terminal block. Once the permit to 

energise the mains supply is in place, energise 

the mains and check the voltage and polarity are 

correct before replacing the panel fuse. 

4.  The panel will power up and enter the power-up 

cable check mode (flashing System Fault LED). 
After about 60 seconds, if all circuits are 

determined to be healthy and no other faults are 

present, the panel should be silent with only the 

Power Supply On indication illuminated. 
If any zones remain in fault after the cable check 

mode has ended, do the following: 

a)  Power down the panel. 
b)  Check that the correct EOL device is 

fitted in the zone terminals. 

c)  Repeat the power-up process. 

5.  Turn the Access Keyswitch to “1” and press the 

Test Display button. The panel should respond 

by  illuminating  all indications and sounding the 

buzzer. This will continue for a few seconds after 

the button is released. 

11.6  Configuration 
11.6.1  Basic Default Configuration 

When first powered up, the Precept EN13  can be 

operated in the standard default mode without any 

additional configuration. 
The basic default mode is: 

 

All zones latching fire, non-delay, standard [non-

intrinsically safe] 

 

Fire Routing, Fire Protection and Sounder 

outputs not delayed. 

11.6.2  Site-Specific Configuration 

It is possible to tailor the functionality of the Precept 

EN13  fire alarm panel in line with site-specific 

requirements. Details of the site configurable 

options and the configuration process are provided 

in section 14.1. Charts are provided in the System 

Log Book for planning/recording the actual 

configuration. This configuration is not lost when 

the panel is powered down. 

11.7  Commissioning Procedure 

After completion of the pre-commissioning wiring 

check, power-up and configuration, commission the 

circuits in line with the following guide. 

11.7.1  Alarm Circuits 

1.  Remove the resistor from the first alarm circuit 

OUT  terminals on the Alarm  Relay Board, 

Connect the first alarm circuit outgoing loop 

wiring to the OUT  terminals  and the incoming 

loop wiring to the RETURN terminals, observing 

correct polarity. Check that any alarm fault 

indications clear after a few seconds. 

2.  Use the Alarm Test facility [see 

FIRE

CLASS 

Precept EN13 User Manual] or press Evacuate 

to operate the sounders. Check that all sounders 

connected to the alarm circuit operate. 

3.  Deselect the Alarms Test condition or if 

“Evacuate” was used, press silence alarms to 

stop the sounders operating. 

4.  Repeat steps 1  to  3  for the second and any 

subsequent alarm circuits.  Leave the EOL 

resistor fitted for any unused alarm circuits. 

Summary of Contents for Precept EN13

Page 1: ...UIPMENT FIRECLASS PRECEPT EN13 PUBLICATION FIRECLASS PREC EN13 INST ISSUE No DATE 2 22 07 2021 PAGE 1 of 32 Precept EN13 Fire Detection Alarm Panel Precept EN Repeater Installation Commissioning Manua...

Page 2: ...RY DEFAULT CONFIGURATION FOR ZONES OUTPUTS 22 14 4 ENGINEER S ZONE OUTPUT CONFIGURATION TIME OUT WARNING 22 14 5 INVALID CONFIGURATION CONDITIONS 22 14 6 LIST OF CONFIGURATION DIL SWITCHES AND THEIR F...

Page 3: ...this manual fully before commencing installation The following supporting documentation is also available FIRECLASS Precept EN13 Sales Literature FIRECLASS Precept EN13 Panel Application Guide FIRECLA...

Page 4: ...3 2 1 ZONE CIRCUITS RST SIL EVAC CLASS CHANGE BUZ ACTIVE P A B REPEATER AUX D C 0V OUTPUTS INPUTS EVAC FAULT GND O ZONE OUTPUTS 4 3 2 1 24V 0V 2 1 3 01 05 12 ISSUE 0 CEL C1717 ALARM 4 3 2 1 CIRCUITS...

Page 5: ...ACKBOX N L M a in s F u s e R ep la ce Sa m e Ty pe W ith RATING LABEL EARTH POST EARTH BAR MAINS TERMINAL ASSEMBLY RELAY BOARD Fu se In pu t Se ria l N o Pa rt N o Pr od uc t St an da rd s A pp ro va...

Page 6: ...EQUIPMENT FIRECLASS PRECEPT EN13 PUBLICATION FIRECLASS PREC EN13 INST ISSUE No DATE 2 22 07 2021 PAGE 6 of 32 Figure 4 8 16 Zone Precept EN13 panel General Assembly with optional clock module...

Page 7: ...iagram Connect to Aux DC 24V 24Vdc relay Typical zonal output wiring Field relay spec Coil resistance 2 6k to 4 5k Ohms Voltage 24Vdc Nom min 18V max 30V Fitted with suppression diode as shown Relay f...

Page 8: ...les from Panel motherboard Each Alarm circuit from the panel motherboard is connected to the IN terminals on the Alarm Relay Board Each Alarm Circuit is wired out to the sounders from the OUT terminal...

Page 9: ...le on selected panel Alarm Circuits 1 2 3 4 Aux DC 24V 0V SIL Inputs Outputs Repeater EVAC RST DIS EVAC A B GND Reset N C Inputs SIL Silence alarms EVAC Evacuate RST Reset Outputs DIS Disablement acti...

Page 10: ...Terminals Power Supply LED indicators OUTPUT OK Battery Charger Fault Charger Fault Mains Fault J18 Earth Fault Monitoring Link Secondary AC from transformer C1631 Repeater Interface Alarm Circuits Ma...

Page 11: ...tion resistance is greater than or equal to 1 the Batt Charge fault LED is illuminated and the Fault Output is operated The circuitry also protects against reversed connection of the batteries 9 2 Vis...

Page 12: ...eat care when lifting and transporting batteries For weights above 24 kilos lifting aids should be used DANGER Do NOT attempt to remove the battery lid or tamper with the internal workings of the batt...

Page 13: ...n an area that is clean dry and dust free where they will not be damaged You can place them inside the original packing box but you must ensure that sufficient soft packing is used to keep the door an...

Page 14: ...y 26 Connect the blue battery lead between the positive red terminal of the left hand battery and the negative black terminal of the right hand battery Note that the batteries will not power the panel...

Page 15: ...should be checked for correct audibility as specified in BS5839 1 using the Evacuate function 2 Detection zones should be commissioned next The purpose is to establish the correct functioning of each...

Page 16: ...ise the mains and check the voltage and polarity are correct before replacing the panel fuse 4 The panel will power up and enter the power up cable check mode flashing System Fault LED After about 60...

Page 17: ...nearest the panel operate each manual call point and detection device on the zone in turn o After operation of each device confirm The fire indication is provided on the panel on the correct zone The...

Page 18: ...ed out at the appropriate time in conjunction with the engineer responsible for the fire protection system 11 7 6 Ancillary inputs Remote Silence Alarms Reset and Evacuate inputs should each be tested...

Page 19: ...isabled Fault Routing Fault Disabled Yellow Flashes for a fault on the Fault Routing Output Steady when Fault Routing Output is disabled POWER SUPPLY ON FIRE FIRE ROUTING ACTIVE GENERAL FAULT POWER SU...

Page 20: ...ked and if silence before reset is configured sounders are silenced Silence Buzzer 1 Press to stop the buzzer sounding in fire or fault conditions Always available 2 In 2 Stage Delay Mode with stage 1...

Page 21: ...and the panel buzzer will silence A pulsing indication cursor will appear either on the Zone 1 Fault Disabled LED or the Sounder Fault Disabled LED Test depending upon which configuration DIL switch i...

Page 22: ...e o The panel buzzer will sound o The Cursor indication will clear o Configuration will be inhibited To clear the invalid condition check the configuration switches SW1 4 to SW1 8 on the motherboard a...

Page 23: ...1 minute within the range 0 9 minutes See Table 1 Motherboard Delay Switch Settings Table 1 Motherboard Delay Switch Settings Delay Duration SW2 2 SW2 3 SW2 4 SW2 5 NONE Off Off Off Off 1 minute On Of...

Page 24: ...14 8 Configuring the Fire Routing Fire Protection and Fault routing O Ps To configure the Fire Routing Output to volt free relay contacts remove links J10 J11 and J12 These links are combined in a sin...

Page 25: ...to 59 Press SELECT ON Time Set display HH MM SS ON Time SS flashing Press ENABLE or DISABLE to change SS to desired value 00 to 59 To set Day Night Mode Off Time Press SELECT to access day night OFF...

Page 26: ...or EEPROM1 EEPROM 0 ERROR or EEPROM 1 ERROR Note Both EEPROMs can be erased by the following procedure 1 Power the panel down 2 Place the WP DIL switch in the ON position 3 Power the panel back up 4...

Page 27: ...15 4 C1651 Clock Module PCB Features Figure 10 llustrates the PCB features referred to elsewhere in the documentation Figure 10 C1651 Clock Module PCB LK1 Select Operating Mode LK1 S1 WP ZERO 1 2 ON D...

Page 28: ...Voltage 230Vac 10 15 Cable requirements Minimum of 1mm2 copper protected by a 5A fuse Power Supply Output Specification Panel Repeater AC powered 2 4 zone 8 zone 16 zone 2 4 8 16 zone Maximum Short T...

Page 29: ...off PS12120 12V 12Ah 2 off PS12120 12V 12Ah 2 off PS12120 12V 12Ah 2 off PS1230 12V 3 4Ah Battery size mm L HT H W L 151 W 98 H 94 HT 100 L 151 W 98 H 94 HT 100 L 151 W 98 H 94 HT 100 L 133 W 67 H 60...

Page 30: ...characteristics Performance under fire conditions Pass Response delay response time to fire Pass Operational reliability Pass Durability of operational reliability Temperature resistance Pass Durabil...

Page 31: ...5 EN BSEN 54 4 Power supply equipment for fire detection and fire alarm systems for buildings List of essential characteristics Performance under fire conditions Pass Operational reliability Pass Dura...

Page 32: ...2 07 2021 2021 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice Tyco Fire Security...

Reviews: