background image

EQUIPMENT:

   

FIRE

CLASS 

PRECEPT EN13

 

PUBLICATION:

  

FIRECLASS PREC EN13 INST

 

ISSUE No. & DATE:

 

2     22/07/2021

 

PAGE 21 of 32 

14.   Operating the Engineer’s 

functions 

14.1  Engineer’s Zone/Output Configuration 

Process: 

Various  configurable  options associated with the 

zone circuits  and outputs can be programmed  via 

the Engineer’s Configuration Mode, enabled via DIL 

switches on the panel motherboard. These are: 

o

  Configure zones as delayed zones. 

o

  Configure zones for use with I.S. 

barriers/isolators. 

o

  Configure zones as latching/non-latching fire 

indication. 

o

  Configure zones to short circuit fire mode. 

o

  Configure outputs to be delayed. 

Note: The DIL switch labelled Configure M/S Zones 

is not used on the Precept EN13 panels. 

14.2  Zone or Output Configuration 
1.  Select a programmable configuration mode: 

o

  Enable the controls on the display, by turning 

the Access Keyswitch on the panel display to 

the “1” position. 

o

  Ensure the panel is in the quiescent state (no 

faults or alarms). 

o

  Open the panel door and locate the 

appropriate DIL switch on the motherboard 

[

Config Non-latch Zones; Config I.S. Zones; 

Config Delay Zones; Config Delay O/Ps

] and 

move the switch to the ON position. 

  The 

CONFIG ENABLED

  LED on the 

motherboard will illuminate. 

  The 

System Fault

  LED  on the display  will 

flash and the buzzer will sound. 

  The 

Select

 LED on the display will pulse. 

  The panel will indicate the current status of 

the selected programmable configuration 

mode on the yellow 

fault/disabled

 LEDs on 

the Zones, Sounders, Fire Routing and Fire 

Protection outputs 

(dependent on 

configuration mode selected). 
An illuminated LED denotes that the relevant 

circuit  is already configured to the selected 

mode. 
An extinguished  LED  denotes that the 

relevant circuit  is not configured to the 

selected mode. 

o

  Close the panel door to allow access to the 

buttons on the display. 

2.  Select a zone or output to be configured: 

o

  On the panel display, press the Select On/Off 

button to enable the Select Mode. 

  The Select LED will become steady and the 

panel buzzer will silence. 

  A pulsing indication [cursor] will appear either 

on the Zone 1 Fault/Disabled LED or the 

Sounder Fault/Disabled LED/Test depending 

upon which configuration DIL switch is 

selected. 

o

  Use the Select 

 

and Select↓ buttons to scroll 

the cursor indication  through the selectable 

options; 

  For zonal configuration, through all zones 

sequentially  in  forward  [Select↓]  or  re

verse 

[Select ↑] sequence starting at zone 1.

 

  For Output Delay configuration, through 

Sounders, Fire Protection and Fire Routing 

outputs  in  forward  [Select↓]  or  reverse 

[Select ↑] sequence starting at Sounders.

 

3.  To change the configuration of a selected 

zone or output: 

With the cursor flashing on the selected zone or 

output: 

  Pressing  the ENABLE button will apply the 

configuration to the selected zone/output 

causing the associated fault/disabled LED to 

illuminate steady (the cursor will continue to 

flash intermittently). 

  Pressing  the DISABLE button will clear the 

configuration and restore default  operation. 

The fault/disabled LED will extinguish (the 

cursor will continue to flash intermittently). 
By repeating steps 1  and  3, any number of 

zones and/or outputs can be configured. 

Note: Any changes to the configuration take 

effect immediately and do not require a 

separate operation to be stored. Changes are 

stored in EEPROM and are not lost when the 

panel is powered down. 

4.  To quit the programmable configuration 

mode: 

o

  Open the panel door and return the selected 

Config DIL switch on the motherboard to the 

OFF position. 

  The 

CONFIG ENABLED

  LED on the 

motherboard will clear, the panel buzzer will 

silence and the flashing System Fault 

indication and zone/output configuration 

status indications on the display will clear as 

will the cursor and the Select indications. Any 

current alarms, fault or disablements, will be 

re-indicated along with any active status 

indications [Delay on etc.]. 

o

  Close and lock the panel door. 

o

  Return the ACCESS Keyswitch  to the “0” 

position to disable the controls on the display. 

IMPORTANT NOTE: WHILE THE PANEL IS 

IN THE ENGINEER’S ZONAL/OUTPUT 

CONFIGURATION MODE, ALL ZONAL 

INPUTS ARE IN PERMANENT RESET AND 

OUTPUTS ARE INHIBITED -  THE PANEL 

WILL NOT RESPOND TO ANY FIRE ALARM. 

Summary of Contents for Precept EN13

Page 1: ...UIPMENT FIRECLASS PRECEPT EN13 PUBLICATION FIRECLASS PREC EN13 INST ISSUE No DATE 2 22 07 2021 PAGE 1 of 32 Precept EN13 Fire Detection Alarm Panel Precept EN Repeater Installation Commissioning Manua...

Page 2: ...RY DEFAULT CONFIGURATION FOR ZONES OUTPUTS 22 14 4 ENGINEER S ZONE OUTPUT CONFIGURATION TIME OUT WARNING 22 14 5 INVALID CONFIGURATION CONDITIONS 22 14 6 LIST OF CONFIGURATION DIL SWITCHES AND THEIR F...

Page 3: ...this manual fully before commencing installation The following supporting documentation is also available FIRECLASS Precept EN13 Sales Literature FIRECLASS Precept EN13 Panel Application Guide FIRECLA...

Page 4: ...3 2 1 ZONE CIRCUITS RST SIL EVAC CLASS CHANGE BUZ ACTIVE P A B REPEATER AUX D C 0V OUTPUTS INPUTS EVAC FAULT GND O ZONE OUTPUTS 4 3 2 1 24V 0V 2 1 3 01 05 12 ISSUE 0 CEL C1717 ALARM 4 3 2 1 CIRCUITS...

Page 5: ...ACKBOX N L M a in s F u s e R ep la ce Sa m e Ty pe W ith RATING LABEL EARTH POST EARTH BAR MAINS TERMINAL ASSEMBLY RELAY BOARD Fu se In pu t Se ria l N o Pa rt N o Pr od uc t St an da rd s A pp ro va...

Page 6: ...EQUIPMENT FIRECLASS PRECEPT EN13 PUBLICATION FIRECLASS PREC EN13 INST ISSUE No DATE 2 22 07 2021 PAGE 6 of 32 Figure 4 8 16 Zone Precept EN13 panel General Assembly with optional clock module...

Page 7: ...iagram Connect to Aux DC 24V 24Vdc relay Typical zonal output wiring Field relay spec Coil resistance 2 6k to 4 5k Ohms Voltage 24Vdc Nom min 18V max 30V Fitted with suppression diode as shown Relay f...

Page 8: ...les from Panel motherboard Each Alarm circuit from the panel motherboard is connected to the IN terminals on the Alarm Relay Board Each Alarm Circuit is wired out to the sounders from the OUT terminal...

Page 9: ...le on selected panel Alarm Circuits 1 2 3 4 Aux DC 24V 0V SIL Inputs Outputs Repeater EVAC RST DIS EVAC A B GND Reset N C Inputs SIL Silence alarms EVAC Evacuate RST Reset Outputs DIS Disablement acti...

Page 10: ...Terminals Power Supply LED indicators OUTPUT OK Battery Charger Fault Charger Fault Mains Fault J18 Earth Fault Monitoring Link Secondary AC from transformer C1631 Repeater Interface Alarm Circuits Ma...

Page 11: ...tion resistance is greater than or equal to 1 the Batt Charge fault LED is illuminated and the Fault Output is operated The circuitry also protects against reversed connection of the batteries 9 2 Vis...

Page 12: ...eat care when lifting and transporting batteries For weights above 24 kilos lifting aids should be used DANGER Do NOT attempt to remove the battery lid or tamper with the internal workings of the batt...

Page 13: ...n an area that is clean dry and dust free where they will not be damaged You can place them inside the original packing box but you must ensure that sufficient soft packing is used to keep the door an...

Page 14: ...y 26 Connect the blue battery lead between the positive red terminal of the left hand battery and the negative black terminal of the right hand battery Note that the batteries will not power the panel...

Page 15: ...should be checked for correct audibility as specified in BS5839 1 using the Evacuate function 2 Detection zones should be commissioned next The purpose is to establish the correct functioning of each...

Page 16: ...ise the mains and check the voltage and polarity are correct before replacing the panel fuse 4 The panel will power up and enter the power up cable check mode flashing System Fault LED After about 60...

Page 17: ...nearest the panel operate each manual call point and detection device on the zone in turn o After operation of each device confirm The fire indication is provided on the panel on the correct zone The...

Page 18: ...ed out at the appropriate time in conjunction with the engineer responsible for the fire protection system 11 7 6 Ancillary inputs Remote Silence Alarms Reset and Evacuate inputs should each be tested...

Page 19: ...isabled Fault Routing Fault Disabled Yellow Flashes for a fault on the Fault Routing Output Steady when Fault Routing Output is disabled POWER SUPPLY ON FIRE FIRE ROUTING ACTIVE GENERAL FAULT POWER SU...

Page 20: ...ked and if silence before reset is configured sounders are silenced Silence Buzzer 1 Press to stop the buzzer sounding in fire or fault conditions Always available 2 In 2 Stage Delay Mode with stage 1...

Page 21: ...and the panel buzzer will silence A pulsing indication cursor will appear either on the Zone 1 Fault Disabled LED or the Sounder Fault Disabled LED Test depending upon which configuration DIL switch i...

Page 22: ...e o The panel buzzer will sound o The Cursor indication will clear o Configuration will be inhibited To clear the invalid condition check the configuration switches SW1 4 to SW1 8 on the motherboard a...

Page 23: ...1 minute within the range 0 9 minutes See Table 1 Motherboard Delay Switch Settings Table 1 Motherboard Delay Switch Settings Delay Duration SW2 2 SW2 3 SW2 4 SW2 5 NONE Off Off Off Off 1 minute On Of...

Page 24: ...14 8 Configuring the Fire Routing Fire Protection and Fault routing O Ps To configure the Fire Routing Output to volt free relay contacts remove links J10 J11 and J12 These links are combined in a sin...

Page 25: ...to 59 Press SELECT ON Time Set display HH MM SS ON Time SS flashing Press ENABLE or DISABLE to change SS to desired value 00 to 59 To set Day Night Mode Off Time Press SELECT to access day night OFF...

Page 26: ...or EEPROM1 EEPROM 0 ERROR or EEPROM 1 ERROR Note Both EEPROMs can be erased by the following procedure 1 Power the panel down 2 Place the WP DIL switch in the ON position 3 Power the panel back up 4...

Page 27: ...15 4 C1651 Clock Module PCB Features Figure 10 llustrates the PCB features referred to elsewhere in the documentation Figure 10 C1651 Clock Module PCB LK1 Select Operating Mode LK1 S1 WP ZERO 1 2 ON D...

Page 28: ...Voltage 230Vac 10 15 Cable requirements Minimum of 1mm2 copper protected by a 5A fuse Power Supply Output Specification Panel Repeater AC powered 2 4 zone 8 zone 16 zone 2 4 8 16 zone Maximum Short T...

Page 29: ...off PS12120 12V 12Ah 2 off PS12120 12V 12Ah 2 off PS12120 12V 12Ah 2 off PS1230 12V 3 4Ah Battery size mm L HT H W L 151 W 98 H 94 HT 100 L 151 W 98 H 94 HT 100 L 151 W 98 H 94 HT 100 L 133 W 67 H 60...

Page 30: ...characteristics Performance under fire conditions Pass Response delay response time to fire Pass Operational reliability Pass Durability of operational reliability Temperature resistance Pass Durabil...

Page 31: ...5 EN BSEN 54 4 Power supply equipment for fire detection and fire alarm systems for buildings List of essential characteristics Performance under fire conditions Pass Operational reliability Pass Dura...

Page 32: ...2 07 2021 2021 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice Tyco Fire Security...

Reviews: