EQUIPMENT:

   

FIRE

CLASS 

PRECEPT EN13

 

PUBLICATION:

  

FIRECLASS PREC EN13 INST

 

ISSUE No. & DATE:

 

2     22/07/2021

 

PAGE 22 of 32 

14.3  To Restore the Factory Default 

Configuration for Zones & Outputs: 

  Open the panel door and locate the DIL 

switches SW1-4 to SW1-8 on the motherboard 

[Config Non-latch Zones; Config I.S. Zones; 

Config M/S Zones; Config Delay Zones; Config 

Delay O/Ps] and move the switch actuator on 

each switch to the On position. 

o

  The Config Enabled LED on the motherboard 

will flash. 

o

  The Panel’s System Fault LED will flash and 

the buzzer will operate. 

o

  Any standing fault or disablement indications 

will clear. 

o

  It will not be possible to enter the Select Mode. 

  Press the Disable button on the panel’s display. 

  Return DIL switches 1-4 to 1-8 to the OFF 

position. 

o

  The Config Enabled LED on the motherboard 

will clear. 

o

  The Panel’s System Fault LED will flash and 

the buzzer will clear. 

o

  The factory default configuration [all zones as 

latching fire, non-delay, standard [non- 

intrinsically safe] will be restored and the Fire 

Routing, Fire Protection and Sounder outputs 

will no longer be delayed 

14.4  Engineer’s Zone/Output Configuration 

Time-out Warning:  

This feature is provided to prevent the panel being 

left in the Zone/Output Configuration condition. 

  1 minute after the last button press: 

o

  The panel buzzer will restart. 

o

  The Select LED will flash. 

o

  The System Fault LED will continue flashing. 

  Press the Select On/Off button to continue with 

the configuration process otherwise quit the 

configuration process as described in 14.2 step 

4. 

14.5  Invalid Configuration conditions: 

  Invalid condition: If two  or more configuration 

switches  on the motherboard are in the ON 

position at the same time: 

o

  The Config LED on the motherboard will flash. 

o

  The System Fault and Select LEDs on the 

display will flash. 

o

  The fault relay will operate. 

o

  The panel buzzer will sound. 

o

  The Cursor indication will clear. 

o

  Configuration will be inhibited. 

  To clear the invalid condition check the 

configuration switches [SW1-4 to SW1-8] on the 

motherboard and ensure that only one is 

selected to ON. 

  Invalid condition: Selecting any config mode 

switch [SW1-4 to SW1-8] to the ON  position 

whilst the panel is in the fire condition: 

o

  The Config LED on the motherboard will flash. 

o

  The System Fault and Select LEDs on the 

display will flash. 

o

  The panel buzzer will sound. 

o

  The Cursor indication will clear. 

o

  Configuration will be inhibited. 

  To clear the invalid condition, select the config 

switch to OFF. Reset the fire alarm condition 

before attempting the configuration process 

again. 

14.6  List of configuration DIL switches and 

their functions 

 

SW1-1 - Inhibit F/P on NLZ

:  

Selects Fire Protection relay to operate 

or

 not to 

operate for a fire condition on any zone 

configured to non-latched mode.  

o

  OFF Fire Protection relay operates for a fire 

condition on any zone configured to non-

latched mode. 

o

  ON: Fire Protection relay does not operate for 

a fire condition on any zone configured to non-

latched mode. 

o

  [Not EN54 compliant function]. 

 

 

S/W1-2 - Delay Alarm Sil & Rst:  

o

  OFF: Silence and reset available as normal. 

o

  ON: Prevents alarms being silenced or reset 

for a period of 3 minutes after a fire alarm 

condition occurs. 

[Not EN54 compliant function]. 
 

 

SW1-3 - Delay On Auto:  

o

  OFF: Automatically turn off the delay mode 

once a day at the set time [the delay mode first 

being turned on manually]. 

o

  ON: Automatically turn the delay mode on 

once a day and off once a day at the set times. 

Requires optional clock module. 
 

 

SW1-4 - Config Non-Latch Zones:  

o

  OFF: Configuration mode disabled. 

o

  ON: Enables selected zones to be configured 

to non-latching fire mode via the Engineer’s 

Select feature.  

[Not EN54 compliant function]. 

 

 

SW1-5 - Config I/S Zones:  

o

  OFF: Configuration mode disabled. 

o

  ON: Enables selected zones to be configured 

to Intrinsically Safe alarm thresholds and 

passive end of line fault monitoring via the 

Summary of Contents for Precept EN13

Page 1: ...UIPMENT FIRECLASS PRECEPT EN13 PUBLICATION FIRECLASS PREC EN13 INST ISSUE No DATE 2 22 07 2021 PAGE 1 of 32 Precept EN13 Fire Detection Alarm Panel Precept EN Repeater Installation Commissioning Manua...

Page 2: ...RY DEFAULT CONFIGURATION FOR ZONES OUTPUTS 22 14 4 ENGINEER S ZONE OUTPUT CONFIGURATION TIME OUT WARNING 22 14 5 INVALID CONFIGURATION CONDITIONS 22 14 6 LIST OF CONFIGURATION DIL SWITCHES AND THEIR F...

Page 3: ...this manual fully before commencing installation The following supporting documentation is also available FIRECLASS Precept EN13 Sales Literature FIRECLASS Precept EN13 Panel Application Guide FIRECLA...

Page 4: ...3 2 1 ZONE CIRCUITS RST SIL EVAC CLASS CHANGE BUZ ACTIVE P A B REPEATER AUX D C 0V OUTPUTS INPUTS EVAC FAULT GND O ZONE OUTPUTS 4 3 2 1 24V 0V 2 1 3 01 05 12 ISSUE 0 CEL C1717 ALARM 4 3 2 1 CIRCUITS...

Page 5: ...ACKBOX N L M a in s F u s e R ep la ce Sa m e Ty pe W ith RATING LABEL EARTH POST EARTH BAR MAINS TERMINAL ASSEMBLY RELAY BOARD Fu se In pu t Se ria l N o Pa rt N o Pr od uc t St an da rd s A pp ro va...

Page 6: ...EQUIPMENT FIRECLASS PRECEPT EN13 PUBLICATION FIRECLASS PREC EN13 INST ISSUE No DATE 2 22 07 2021 PAGE 6 of 32 Figure 4 8 16 Zone Precept EN13 panel General Assembly with optional clock module...

Page 7: ...iagram Connect to Aux DC 24V 24Vdc relay Typical zonal output wiring Field relay spec Coil resistance 2 6k to 4 5k Ohms Voltage 24Vdc Nom min 18V max 30V Fitted with suppression diode as shown Relay f...

Page 8: ...les from Panel motherboard Each Alarm circuit from the panel motherboard is connected to the IN terminals on the Alarm Relay Board Each Alarm Circuit is wired out to the sounders from the OUT terminal...

Page 9: ...le on selected panel Alarm Circuits 1 2 3 4 Aux DC 24V 0V SIL Inputs Outputs Repeater EVAC RST DIS EVAC A B GND Reset N C Inputs SIL Silence alarms EVAC Evacuate RST Reset Outputs DIS Disablement acti...

Page 10: ...Terminals Power Supply LED indicators OUTPUT OK Battery Charger Fault Charger Fault Mains Fault J18 Earth Fault Monitoring Link Secondary AC from transformer C1631 Repeater Interface Alarm Circuits Ma...

Page 11: ...tion resistance is greater than or equal to 1 the Batt Charge fault LED is illuminated and the Fault Output is operated The circuitry also protects against reversed connection of the batteries 9 2 Vis...

Page 12: ...eat care when lifting and transporting batteries For weights above 24 kilos lifting aids should be used DANGER Do NOT attempt to remove the battery lid or tamper with the internal workings of the batt...

Page 13: ...n an area that is clean dry and dust free where they will not be damaged You can place them inside the original packing box but you must ensure that sufficient soft packing is used to keep the door an...

Page 14: ...y 26 Connect the blue battery lead between the positive red terminal of the left hand battery and the negative black terminal of the right hand battery Note that the batteries will not power the panel...

Page 15: ...should be checked for correct audibility as specified in BS5839 1 using the Evacuate function 2 Detection zones should be commissioned next The purpose is to establish the correct functioning of each...

Page 16: ...ise the mains and check the voltage and polarity are correct before replacing the panel fuse 4 The panel will power up and enter the power up cable check mode flashing System Fault LED After about 60...

Page 17: ...nearest the panel operate each manual call point and detection device on the zone in turn o After operation of each device confirm The fire indication is provided on the panel on the correct zone The...

Page 18: ...ed out at the appropriate time in conjunction with the engineer responsible for the fire protection system 11 7 6 Ancillary inputs Remote Silence Alarms Reset and Evacuate inputs should each be tested...

Page 19: ...isabled Fault Routing Fault Disabled Yellow Flashes for a fault on the Fault Routing Output Steady when Fault Routing Output is disabled POWER SUPPLY ON FIRE FIRE ROUTING ACTIVE GENERAL FAULT POWER SU...

Page 20: ...ked and if silence before reset is configured sounders are silenced Silence Buzzer 1 Press to stop the buzzer sounding in fire or fault conditions Always available 2 In 2 Stage Delay Mode with stage 1...

Page 21: ...and the panel buzzer will silence A pulsing indication cursor will appear either on the Zone 1 Fault Disabled LED or the Sounder Fault Disabled LED Test depending upon which configuration DIL switch i...

Page 22: ...e o The panel buzzer will sound o The Cursor indication will clear o Configuration will be inhibited To clear the invalid condition check the configuration switches SW1 4 to SW1 8 on the motherboard a...

Page 23: ...1 minute within the range 0 9 minutes See Table 1 Motherboard Delay Switch Settings Table 1 Motherboard Delay Switch Settings Delay Duration SW2 2 SW2 3 SW2 4 SW2 5 NONE Off Off Off Off 1 minute On Of...

Page 24: ...14 8 Configuring the Fire Routing Fire Protection and Fault routing O Ps To configure the Fire Routing Output to volt free relay contacts remove links J10 J11 and J12 These links are combined in a sin...

Page 25: ...to 59 Press SELECT ON Time Set display HH MM SS ON Time SS flashing Press ENABLE or DISABLE to change SS to desired value 00 to 59 To set Day Night Mode Off Time Press SELECT to access day night OFF...

Page 26: ...or EEPROM1 EEPROM 0 ERROR or EEPROM 1 ERROR Note Both EEPROMs can be erased by the following procedure 1 Power the panel down 2 Place the WP DIL switch in the ON position 3 Power the panel back up 4...

Page 27: ...15 4 C1651 Clock Module PCB Features Figure 10 llustrates the PCB features referred to elsewhere in the documentation Figure 10 C1651 Clock Module PCB LK1 Select Operating Mode LK1 S1 WP ZERO 1 2 ON D...

Page 28: ...Voltage 230Vac 10 15 Cable requirements Minimum of 1mm2 copper protected by a 5A fuse Power Supply Output Specification Panel Repeater AC powered 2 4 zone 8 zone 16 zone 2 4 8 16 zone Maximum Short T...

Page 29: ...off PS12120 12V 12Ah 2 off PS12120 12V 12Ah 2 off PS12120 12V 12Ah 2 off PS1230 12V 3 4Ah Battery size mm L HT H W L 151 W 98 H 94 HT 100 L 151 W 98 H 94 HT 100 L 151 W 98 H 94 HT 100 L 133 W 67 H 60...

Page 30: ...characteristics Performance under fire conditions Pass Response delay response time to fire Pass Operational reliability Pass Durability of operational reliability Temperature resistance Pass Durabil...

Page 31: ...5 EN BSEN 54 4 Power supply equipment for fire detection and fire alarm systems for buildings List of essential characteristics Performance under fire conditions Pass Operational reliability Pass Dura...

Page 32: ...2 07 2021 2021 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice Tyco Fire Security...

Reviews: