EQUIPMENT:
FIRE
CLASS
PRECEPT EN13
PUBLICATION:
FIRECLASS PREC EN13 INST
ISSUE No. & DATE:
2 22/07/2021
PAGE 28 of 32
16. Mechanical, Electrical & Environmental Specification
Mechanical
Specification
Panel
Repeater (AC powered)
2/4 zone
8 zone
16 zone
2, 4, 8 & 16 zone
Size [mm]
Height:
Width:
Depth:
370
325
126
370
325
126
370
325
126
370
325
126
Weight excluding
batteries:
6.8Kg
7.2Kg
7.2Kg
6.65Kg
Mains Input
Specification
Panel
Repeater (AC powered)
2/4 zone
8 zone
16 zone
2, 4, 8 & 16 zone
Maximum Input
Power:
85W
165W
165W
85W
Protection:
[Warning: Replace
only with identical
type & rating of
BEAB or VDE
approved fuse]
T1A
H250V
[1A anti-surge]
T3.15A
H250V
[3.15A anti-
surge]
T3.15A
H250V
[3.15A anti-
surge]
T1A
H250V
[1A anti-surge]
Voltage:
10%/-15%
Cable
requirements:
Minimum of 1mm
2
copper protected by a 5A fuse.
Power Supply
Output
Specification
Panel
Repeater (AC powered)
2/4 zone
8 zone
16 zone
2, 4, 8 & 16 zone
Maximum Short
Term Current
Output
(I max b)
1.5A
3A
3A
1.5A
Maximum
Continuous
Current Output
(I max a)
0.6A
2A
2A
0.6A
Minimum Output
Current
(I min)
N/A
(PSU is integrated into the motherboard)
Voltage Output,
Mains On
26.9 - 28.0V (27.3V nominal, temperature dependent)
Maximum Current
Output, Mains
Failed
1.5A
3A
3A
1.5A
Voltage Output,
Mains Failed
[* at full load]
20.0* - 28.0V
20.0* - 28.0V
20.0* - 28.0V
No Auxiliary Output Provided
Max Ripple
including switching
spikes[full
load/battery
disconnected]
200mV peak to peak
Output Voltage
adjustment
Factory Set
Output protection:
Electronic current limiting
Common fault
output:
N/A (PSU is integrated into the motherboard)
Mains failed fault